Add to Cart
IG-541 fire extinguishing agent is a mixture of nitrogen, argon, and carbon dioxide in a specific mass ratio. Common ratios are as follows:
Nitrogen (N2): approximately 48.8% to 55.2% (some sources also show it to be about 50% or 52%)
Argon (Ar): approximately 37.2% to 42.8% (some sources also show it to be about 40% or 42%)
Carbon dioxide (CO2): approximately 7.6% to 8.4% (some sources also show it to be about 8%)
These gases are naturally present in the atmosphere and have abundant sources. They do not cause environmental pollution.
No. | Specification | Technical Parameter | |||
1 | Working Pressure | 20MPa | 30MPa | ||
2 | Device Model | HMP20/80 | HMP20/140 | HMP30/80 | HMP30/140 |
3 | Capacity | 80Ltr | 140Ltr | 80Ltr | 140Ltr |
4 | Filling Capacity of Gas | 23.9kg | 42kg | 33.2kg | 58.2kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ406mm | Φ267mm | Φ356mm |
6 | Height of Cylinder | 1710mm | 1460mm | 1870mm | 1925mm |
7 | Spraying Time | ≤120s | |||
8 | Filling Rate | 0.299kg/L | 0.300kg/L | 0.415kg/L | 0.201kg/L |
9 | Power | DC24V/1.6A | |||
10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | |||
11 | Condition of Reserving Room for Container | temperature: -20~50℃ | |||
12 | Max Working Pressure | 23.2MPa | 36.6MPa | ||
13 | Min Working Pressure | 18MPa | 27MPa |
Packaging and Shipping for Inert Gas Fire Suppression System
Our Inert Gas Fire Suppression System is safely and securely packaged in our own custom designed crates in order to ensure that the system arrives in perfect condition. Our custom crates are designed to protect the system from all types of shipping impacts, such as vibration, shock, and extreme temperatures. All of our packaging materials are also optimized for air, land, and sea shipments, so you can be sure that your system will arrive safely no matter what type of shipping you use.