Add to Cart
Introduction
TA2100 a wide-range, multi-value and high-precision calibrator, can accurately output ultra-precision AC voltage, current and power, with two specifications of 0.02% and 0.05%.
It is suitable for calibrating AC power analyzers, AC power meters, AC voltmeters, and AC ammeters.
Features
Electrical Parameters Output: Voltage is up to 1100 V, current is up to 110 A at a frequency of 45 Hz ~ 70 Hz (400 Hz optional).
AC power output: calibrate the active power, reactive power, apparent power and power factor of the meter under test.
Value Adjustment Method: Fixed-point, rotary encoder, step and potentiometer (option).
Output Switch: The output can be turned on/off arbitrarily by one-touch operation.
Statistical analysis function: Automatically record the maximum and minimum values of electricity, calculate the average value and standard deviation, and analyze the stability.
High reliability of the whole machine: with overload protection, voltage short circuit protection, current open circuit protection, overheating protection, etc.
Excellent Human-Computer Interaction: Large LCD touch screen display, touch and button operation modes, easy for users to measure manually.
Specification
AC Voltage Output ACV
Output Range: 0.3 V ~ 1100 V; Resolution: 0.001 %*RG;
Short circuit protection, overload protection
AC Current Output ACI
Output Range: 0.3 mA ~ 110 A; Resolution: 0.001 %*RG;
Open circuit protection, overload protection
AC Small Voltage Output
Output Range: 0.5 mV ~ 6 V; Resolution: 0.001 %*RG;
Short circuit protection, overload protection; This output is suitable for the small signal input of the sensor of the power analyzer.
AC Power Output
Output Range of AC Power: Combination of AC voltage range and AC current range.
Range of Power Factor: -1.0000…0.0000…+1.0000
Active Power (|cosφ| ≥0.5), Reactive Power (|sinφ| ≥0.5)
Frequency and Phase
Range of Frequency: 45.000 0 Hz ~ 70.000 0 Hz
Resolution of Frequency: 0.000 1 Hz
Accuracy of Frequency: 0.005 Hz
Range of Phase: 0.000 ° ~ 359.999 °
Resolution of Phase: 0.001 °
Accuracy of Phase: 0.05 ° (0.05%), 0.02 ° (0.02%)