4.5KA Mini Circuit Breaker SB6HS Single Phase 10A,63A MCB Electrical Appliance


Application:

♦ Short-circuit protection

♦ Isolation function

♦ Overload protection

♦ Indication function of contact position

♦ Support 35mm Din-rail installation

♦ Support top incoming and bottom outgoing wiring type, or bottom incoming and top outgoing wiring type

♦ Able to select electrical accessories and achieve distant indication of MCB condition; breaking, closed, and fault tripping

♦ Able to select electrical accessories and realize under-voltage and over-voltage protection of MCB and distant shunt release


Instantaneous tripping characteristic:

Circuit breaker SB6 are designed for protection of distribution and branch circuits, having different load;

♦ Curve B----Device should not work in 0.1 second at current 3 In; at current 5 In should work in less than 0.1S

♦ Curve C---- Device should not work in 0.1 second at current 5 In; at current 10 In should work in less than 0.1S

♦ Curve D---- Device should not work in 0.1 second at current 10 In; at current 20 In should work in less than 0.1S



Over-current operating characteristics:

No.Rated current of release (A)Initial stateTest currentSpecified timeResult to be obtainedRemarks
11~63code state1.13 Int ≤ 1hNon-trip
21~63upon the previous test1.45 Int < 1htripsetting current up to specified value steadily in 5s
3In ≤ 32code state2.55 In1s <t <60strip
In > 32code state2.55 In1s <t <120strip
41~63code state3 Int ≤0.1sNon-tripB type
1~63code state5 Int <0.1stripB type
1~63code state5 Int ≤0.1sNon-tripC type
1~63code state10 Int <0.1stripC type
1~63code state10 Int ≤0.1sNon-tripD type
1~63code state20 Int <0.1stripD type

The Number of Poles:


Dimensions:


Specifications:

Poles1P,1P+N, 2P, 3P, 3P+N, 4P
Electrical specification
Rated current(A) In1-63
Rated frequency(Hz)50/60
Rated working voltage(V) Ue1P:230/400~, 2/3/4P: 400~
Rated insulated voltage(V) Ui500
Impulse withstand voltage(KV) Uimp6
Rated short-circuit breaking capacity(KA) Icn

4.5

Instantaneous tripping typeB,C,D
Maximum working voltage Umax440
Minimum working voltage Umin12
Dielectric test voltage (kv)2
Service life Mechanical standard value10000
(O-C) Electrical Standard value4000
Control and indication:
Shunt release (SHT)Optional
Undervoltage release(UVT)Optional
Auxiliary contact(AUX)Optional
Alarm contact(ALT)Optional
Contact position indicatorDefault
Fault indicationNone
Connection and installation:
Ambient temperature (with daily average≤35℃)-5℃~+40℃
Protection degree All sidesIP40
Connection terminalIP20
Wire(㎟)16
Busbar(㎟)16
MountingCable/Busbar
Pollution degree2
Reference temperature for setting of thermal element(℃)30
Storage temperature(℃)-25℃~+70℃
Tightening torque3.0
ConnectionTop and Bottom
Dimensions(mm) a(1P/2P/3P/4P)17.5/35/52.5/70
b(1P/2P/3P/4P)83/83/83/83
(WxHxL) c(1P/2P/3P/4P)67/67/67/67