AC choke output reactor used for 5.5kw 7.5kw 11kw 15kw AC drive
Rated operating power: 380V/690V/1140V
Operating frequency: 50/60Hz
Current range: 5-1600A
Operating ambient temperature: -25℃-50℃
Dielectric Strength: Core-winding,AC 3000V/50Hz/5mA/ free of demage
in 60s (test in factory)
Insulation Resistance: Core-Winding,DC 1000V,Resistance >100M
ohm
Noise: Less than 65dB(to be measured at the point 10 meter away
from the reactor horizontally
Protection class: IP00
Insulation class: F/H
Standard: GB 19212.1-2008GB/T1094.6-2011
Product Parameters
Voltage Range | DC500V-1000V |
Dielectric Strength | Core-Winding, AC 3000V/50Hz/5mA, free of damage in 60s |
Insulation Resistance | Core-Winding, DC 1000V, Resistance > 100M ohm |
Reactor's noise | less than 65dB(to be measured at the point 1 meter away from the reactor horizontally) |
Standard | GB 19212.1-2008 GB/T 1094.6-2011 |
Product Size
It is recommended to use input reactors in the following
circumstances:
1. frequency converters in parallel close connection.
2. line power supply has obvious disturbance from other devices
(interference, over voltage).
3. there is voltage imbalance between the phases of the line power
supply, exceeding 1.8% of the rated voltage.
4. a large number of converters are installed on the same line.
5. reduce cos C overload on the correction capacitor if there is a
power factor correction device in the device.
6. power supply capacity is 60KVA and above, and frequency
converter installation location is within 10M of large capacity
power supply.
7. the frequency converter is powered by a very low impedance line
(10 times higher than the inverter's rated value).