3-Phase Modular UPS With N+X Redundancy Design And Hot-Swappable Modularity 20-200kva
The CNM series modular UPS provides the most compact footprint of
less than 2㎡ with maximum capacity of 900kVA.With best reliability
and high performance, it has been leading the domesticmarket for
years.
CNM series is considered to be the best power protection solution
for large data centers, as well
as for sensitive electronics.
Modular UPS System Features
♦Extendibility:
The greatest difference between a modular UPS and a traditional
single-unit UPS is that it is not necessary to add an identical
unit having the same capacity or replace the mainframe with one
having a higher capacity when the capacity of the entire system
needs to be extended, In stead the capacity be easily extended by
increasing the number of modules.
It is advantageous in that: it satisfies the user’s demand for
capacity extension as required in later stages.The planned
investment can be “changed as required”. And the user’s investment
can grow with the dynamic development of the user’s business. The
cost of primary design can be reduced.
♦Availability:
Extremely high system availability, which is ≥99.9998%1.
1.Its Mean Time between Failures (MTBF) is 1.5 times of the MTBF of
the traditional UPS. Its Mean Time between Component Failures (
MTBCF) is 3 times of the MTBCF of traditional UPS.
2. Failures of a single module will not affect the normal operation
of the system. The user does not have to shut down the system and
wait for repair and UPS failures will not cause losses to the user.
3. Technicians that arrive at the site do not have to locate and
eliminate the failure point but only have to directly replace the
corresponding module. The user can even maintain the system himself
if he has the required spare parts.
4. The Mean Time to Repair (MTTR) is reduced from 2-8h to less than
5 min within which the repair can be completed under the online
status.
5. The simplified stock of spare pars reduces the user’s cost of
use and maintenance and the prices of service contracts.
6. When the system controller fails, the UPS system can still
maintain normal output without switching over to the bypass.
7. The user can maintain the system at any time and does not have
to take routing inspections at regular intervals. The hidden risk
of failures can be reduced.
8. Extremely high reliability and stability ensure optimal
protection of the load.
9. The modular design based on a standard equipment cabinet
provides more conveniences for the installation, debugging,and
relocation of the system, cuts down the workload of construction
design, and reduces the cost of installation.
♦Hot-plug performance:
The power module and monitoring & communication module of the system can be plugged in or plugged out online at will. This will shorten the time that technicians have to spend on maintenance and repairs, greatly simplify the repairing procedures, and provide more conveniences and safety of work.
♦Redundancy:
All power modules in the system equally share the load of the system. Upon a failure of any module, other modules will automatically share the load of this failed module. Each module of the system can run independently. No system controller centralized control of system. An N+1~N+X redundancy system can be constructed as required, reducing the risk factors of the system itself and its load and comprehensively prolonging the duration of UPS protection of the external load.
♦Environmental friendliness:
The total harmonic distortion (THDI) of the input of the UPS system is only 3%, which is far lower than the 33% input harmonic distortion of the 6-pulse silicon controlled rectifier of the traditional single-unit UPS and the 13% input harmonic distortion of the 12-pulse silicon controlled rectifier. Under a linear load, the output THDI is lower than 2%. The harmonic inference against the power network is minimized and the load and power losses of the power network are effectively reduced. With its excellent input parameters and characteristics of a pure resistance with respect to the commercial power network, this is an ideal pollution-free UPS which can be easily fitted to the commercial power network and generators and is close to the load-bearing capacity of the actual network.
Data Sheet
Model | System | CNM-100/10 | CNM-150/15 | CNM-200/20 | CNM-250/25 | CNM-300/30 | CNM-500/50 |
Power module | HM10 | HM15 | HM20 | HM25 | HM30 | HM50 | |
Capacity | System power | 100KVA | 150KVA | 200KVA | 250KVA | 300KVA | 500KVA |
Main line | Connection | three-phase five-wire system | |||||
Rated voltage | 380/400/415VAC | ||||||
Voltage range | -40% to +30% | ||||||
Rated frequency | 50/60HZ | ||||||
Frequency range | 40-70HZ | ||||||
Current harmonic wave distortion | THDI<3% | ||||||
Input power factor | >0.99 | ||||||
Bypass | Rated voltage | 380/400/415VAC | |||||
Voltage range | -20% to +15%(other value out of this range can be set) | ||||||
Rated frequency | 50/60HZ | ||||||
Frequency range | ±1HZ, ±3HZ,±5HZ | ||||||
Battery | Battery cells | 40 batteries(32-44 optional) | |||||
Output | Connection method | three-phase five-wire system | |||||
Rated voltage | 380/400/415VAC | ||||||
Rated frequency | 50/60HZ | ||||||
Voltage accuracy | ±1% | ||||||
Frequency accuracy | 50/60HZ±0.01HZ | ||||||
Voltage harmonic wave distortion | <1%(Linear load); <3%(Non-linear load) | ||||||
Range of frequency synchro | ±3HZ, ±0.5HZ to ±5HZ (other value out of this range can be set) | ||||||
Peak value | ≥3:1 | ||||||
Three phase accuracy | <0.5° | ||||||
Power factor | 1.0 | ||||||
Overload capability | 110%, switch to bypass after 3 hours; 125%, switch to bypass after 30 minutes; 150%, switch to bypass after 5 minutes | ||||||
Efficiency | City electriciy mode | ≥96% | |||||
Battery mode | ≥96% | ||||||
ECO mode | ≥98% | ||||||
Machine system | Wire connection method | support up and down connection | |||||
Protection level | IP20/IP21(optional) | ||||||
Panel display | LCD+LED, super big colorful touch screen | ||||||
Communication interface | RS232,RS485,SNMP,EPO, generator interface | ||||||
Operation environment | Running temp. | -10℃ to 40℃ | |||||
Storage temp. | -25℃ to 70℃ | ||||||
Relative humidity | 0-95% with no condensation | ||||||
Noise(dB) | <55dB | <65dB | |||||
Weight(KG) | Cabinet | 180 | 245 | 470 | |||
Power module | 20 | 21 | 22 | 32 | 36 | 45 | |
Size(W*D*H) mm | Cabinet | 600*900*2000 | 600*1100*2000 | 1300*1100*2000 | |||
Power module | 440*590*134 | 460*790*134 | 510*700*178 |