Discover the pinnacle of power protection for your critical systems with our premier Online Uninterruptible Power Supply (UPS), an essential addition to any server room UPS arsenal. Engineered for reliability and performance, our UPS is designed to ensure that your vital equipment remains operational, even in the face of power disturbances. Boasting a robust Rate Freq of 50/60Hz, this UPS is versatile and adaptable, ready to meet the demands of a wide range of power grid specifications around the world. |
|
Model CNM | 020/10 | 030/15 | 040/20 | 040/10 | 045/15 | 060/15 | 080/20 | 090/15 | 120/20 |
Rate Power | 20KVA/20KW | 30KVA/30KW | 40KVA/40KW | 40KVA/40KW | 45KVA/45KW | 60KVA/60KW | 80KVA/80KW | 90KVA/90KW | 120KVA/120KW |
Main input | |||||||||
Input | 3P5W(3P+N+PE) | ||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Input PF | >0.99 | ||||||||
Current Distortion | THDi<3%(100%Linear load) | ||||||||
Voltage Range | 304-478VAC(L-L)full load;304-228VAC(L-L)power derate from 100%to 75% | ||||||||
Freg.Range | 40-70Hz | ||||||||
Battery | |||||||||
Rate voltage | ±240VDC(adjustable for 32-44 sections) | ||||||||
Charging Capacity | 20%*Pout | ||||||||
Charging Accuracy | ±1% | ||||||||
Bypass | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Voltage Range | Range:-40%-+25%,Settable,default-20%~+15% | ||||||||
Overload | 110%,long time operation;110%<load<125%,5 mins 125%<load<150%,1min;>150%,1second | ||||||||
Inverter | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Output PF | 1 | ||||||||
Voltage Accuracy | ±1.0% | ||||||||
load Response | <5%(20%-80%-20%step load) | ||||||||
Recovery Time | <20ms(0%-100%-0%step load) | ||||||||
Output THDu | <1%(linear load),<5%(non-linear load according to IEC 62040-3) | ||||||||
Overload | 110%,1 hour;125%,10 mins;150%,1min;>150%,200ms | ||||||||
Frequency Accuracy | 0.1% | ||||||||
Synchronize Window | Settable,±0.5Hz-±5Hz,default±3Hz | ||||||||
Slew Rate | Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S | ||||||||
Phase Accuracy | 120°±0.5° | ||||||||
System | |||||||||
Efficiency | Normal Mode≥96%;Battery Mode≥96% | ||||||||
Display | LED+7inch touch LCD | ||||||||
Certification-Safety | IEC62040-1,IEC60950-1 | ||||||||
Certification-EMS | IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) | ||||||||
IP Degree | IP20 | ||||||||
Configuration | USB,RS232,RS485,Dry contact,Cold start | ||||||||
Option | SNMP card,AS400 card,Parallel kit,LBS,Air filter,Bottom entry kit,Wheels kit | ||||||||
Environment | 0-40℃(operation);-25~70(storage);0-95%(Humidity,non-condensing) | ||||||||
Noise(dB)(1meter) | 65dB @100%load,62dB @45%load | ||||||||
Dimension | |||||||||
Cabinet(W*D*H)mm | 482*700*396(9U, wheels not included) | 482*700*662(15U, wheels not included) | 482*700*840(19U, wheels not included) | ||||||
Module(W*D*H)mm | 440*555*85(2U) |
|
1. Technical Support: We offer comprehensive technical support for troubleshooting, setup assistance, and resolving any issues you may encounter with your UPS. Our support team is knowledgeable and ready to help ensure your UPS is functioning optimally. 2. User Manuals and Documentation: Access to a comprehensive library of user manuals, technical specifications, and other documentation to facilitate the installation, operation, and maintenance of your UPS. 3. Training: We provide training sessions for users to understand the proper operation, maintenance, and safety procedures associated with the Online UPS to ensure proficient use and management. Our goal is to ensure that your Online UPS provides the highest level of power protection and to support you with any services you may need throughout the life of the product. |