SUTO S230 Compressed Air Dew Point Transmitter Ex

Brand Name:Zetron
Certification:CE, ISO13485, ISO9001
Model Number:S230
Minimum Order Quantity:1
Delivery Time:3-7 days
Payment Terms:D/A, D/P, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Beijing Beijing China
Address: Room 20E, Block 1-A, Oriental Ginza, No. 48 Dongzhimenwai Avenue, Dongcheng,100007, Beijing, China
Supplier`s last login times: within 33 hours
Product Details Company Profile
Product Details
S230 Compressed Air Dew Point Transmitter for Ex Applications (-100~+20 °C Td)
OVERVIEW
The SUTO S230 / S231 Heavy-Duty Dew Point Transmitters provide reliable, long-term stable dew point monitoring for compressed air and gases in harsh and hazardous applications. The fast response time ensures safe and reliable indication whenever dew points are out of valid ranges.
FEATURES

· S230 For Low Dew Point Applications

The S230 Dew Point Transmitter provides accurate results of a range down to -100 °C Td. This makes it perfectly suitable for special applications where a low dew point needs to be measured.

· Ex Areas Solution

The optional IECEx approval makes it the perfect tool to be used in explosive environment (Ex area). SUTO’s unique dual sensor technology optimizes sensor sensitivity and accuracy by automatically selecting the ideal sensor type for the situation.

· User-Friendly Output Signals

The S230/S231 come ready to use and simple to install with your choice of 4-20mA or Modbus RTU (RS485) outputs. If required, parameters can be quickly monitored through the SUTO service software. The transmitters can also be connected the SUTO S331 (stationary) or S551 (portable) data logger and the data can be transferred for further analysis.


APPLICATION SCENES
  1. Dew point measurement in explosive environments
  2. Outdoor / all-weather flow applications
  3. Explosive environments
SPECIFICATION

MEASUREMENT

Dew Point
Accuracy± 1 °C Td (0 ... 20 °C Td)
± 2 °C Td (-60 ... 0 °C Td)
± 3 °C (-100 ... -60 °C Td)
Selectable units°C, °F, bar(g), MPa(g), psi(g), % rH,
g/m³, mg/m³, G/m³ atm., mg/m³ atm., ppm(v), g/kg, °C Td atm.
Measuring range (model depending)S230: -100 ... +20 °C Td
S231: -50 ... +20 °C Td
SensorPolymer + QCM
Response time t90 (@ 4l/min)-20 °C Td -> -60 °C Td = < 240 s
-60 °C Td -> -20 °C Td = < 30 s
Temperature
Accuracy0.3 °C
Measuring range-30 ... +70 °C
SensorNTC
Reference conditions
Selectable conditionsPressure Dew Point,
Atmospheric Dew Point

SIGNAL INTERFACE & SUPPLY

Analog output
Signal4 ... 20 mA (isolated)
Modbus/RTU
ScalingS230: 4 mA = -100 °C Td;
20 mA = +20 °C Td
S231: 4 mA = -50 °C Td;
20 mA = +20 °C Td
Load250R
Update rate3 / sec
Fieldbus
ProtocolModbus/RTU
Update rate1/s
Supply
Voltage supply15 ... 30 VDC
Current consumption40 mA @ 24 VDC

GENERAL DATA

Konfiguration
PC SoftwareS4C-DP Application
Material
Process connectionStainless steel 1.4301 (SUS 304)
HousingAluminium alloy
SensorPolymer, Ceramic
Miscellaneous
Electrical connectionScrew terminals
Protection classIP67
ApprovalsII 2G Ex db ib IIC T4 Gb
II 2D Ex ib tb IIIC T135°C Db
CE
Process connectionG 1/2“ thread (ISO 228/1)
Weight728 g
Operating conditions
MediumAir, Argon, O₂, N₂, CO₂*
Medium qualityISO 8573-1: 4.6.3 or better
Medium temperature-30 ... +70 °C
Medium humidity≤ 20 °C Td
Operating pressure (model depending)-0.1 ... 1.6 MPa (S230)
-0.1 ... 35 MPa (S231)
Ambient temperature0 ... +50 °C
Ambient humidity0 ... 100 % rH
Storage temperature-20 ... +50 °C
Transport temperature-30 ... +70 ºC
Stated accuracy under following conditions:
Ambient temperature 23 °C ±3 °C
Process temperature 23 °C ±3 °C
Ambient humidity < 95 %, no condensation
Airflow > 2 l/min at sensor tip


China SUTO S230 Compressed Air Dew Point Transmitter Ex supplier

SUTO S230 Compressed Air Dew Point Transmitter Ex

Inquiry Cart 0