150ah 12v Lead Acidy Front Terminal Batteries Solar Panel Deep Cycle Sealed Agm

Brand Name:FOBERRIA
Certification:CE / ISO9001
Model Number:FT12-150-1
Minimum Order Quantity:200pcs
Delivery Time:25-30days
Payment Terms:L/C, T/T, Western Union
Contact Now

Add to Cart

Site Member
Location: Suzhou Jiangsu China
Address: No.188 Chunxu Road ,Economic Development Zon, Kunshan City, Suzhou, Jiangsu Province, China.
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

150ah 12v Lead Acid Battery Front Terminal Batteries Solar Panel Deep Cycle Battery Sealed Agm Battery


>Main Features


● Strong heat dissipation and wide operating temperature range


● Avoid acid mist being separated out,environment friendliness


● Slim shape design and front terminal connection


● Prominent high rate discharge performance


● Optional fire retardant design


● Long designed service life


● Excellent discharge performance Environment friendliness


>Specification
Battery Model No.FBR12-150FT
Nominal Voltage12V
Capacity
(25ºC)
20HR(10.8V)150Ah
10HR(10.5V)132Ah
1HR(9.6V)90Ah
DimensionLength551±2mm
Width110±2mm
Height287±2mm
Total height287±2mm
Approx. Weight48.5kg±4%
Terminal typeF14
Internal resistance
(Fully charged,25ºC)
Approx4.2mΩ
Capacity affected by
temperature(20HR)
40ºC102%
25ºC100%
0ºC85%
-15ºC65%
Self-discharge
(25ºC)
3monthRemaining Capacity:91%
6monthRemaining Capacity:82%
12monthRemaining Capacity:65%
Nominal operating temperature25ºC±3ºC(77ºF±5ºF)
Operating
temperature range
Discharge-15ºC-50ºC(5ºF-122ºF)
Charge-10ºC-50ºC(14ºF-122ºF)
Storage-20ºC-50ºC(-4ºF-122ºF)
Float charging voltage
(25ºC)
13.5 to 13.8V
Temperature compensation:-18mV/ºC
Cyclic charging voltage
(25ºC)
14.5 to 15V
Temperature compensation:-30mV/ºC
Max charging current45A
Max discharging current1200A(5sec.)
Designed floating life(20ºC)12years
>Structure and composition
ComponentPositive plateNegative plateContainerCoverSeparatorElectrolyteSafety valveTerminal
Raw materialLead dioxideLeadABSABSAGMSulfuric acidRubberCopper
>Constant Current Discharge Characteristics(A,25ºC)
F.V/Time10min15min30min60min2h3h4h5h8h10h20h
9.6V31724414689.954.839.031.526.918.515.38.09
9.9V30823914388.654.538.831.326.818.415.28.08
10.2V29523013986.354.038.531.126.618.315.28.05
10.5V28222213684.553.238.330.926.418.215.18.01
10.8V26621013181.951.837.130.025.617.615.07.95

>Constant Power Discharge Characteristics(Watt,25ºC)


F.V/Time10min15min30min60min2h3h4h5h8h10h20h
9.60V342626841641102563545937131822018297.1
9.90V332326201608101063145636831621918296.9
10.2V31862523155998462545336631421718196.6
10.5V30492437152196461645036331221618096.1
10.8V28782308146593460043635230320917995.4

>Discharge diagram
>Application

1. Solar and wind energy storage system;

2. EPS and UPS battery backup;

3. Signal system , emergency lighting system , security system;

4. Telecommunication Equipment;

5. Power source for portable devices or tools.
>FAQ
Q1: How to choose the right battery?

A1: Tell us your demand, then our sales will recommend a suitable battery for you.

Q2. Do you have any MOQ limit?

A2: Yes, we have MOQ for mass production, it depends on the different model numbers. 50-500pcs sample order is available.
for sample checking is available.

Q3. Is it OK to print my logo on the product?

A3: Yes. Please inform us formally before our production and confirm the design firstly based on our sample.

Q4: How to solve the technical problem?

A4: 24 hours after-service consultancy just for you and to make your problem to solve easily.

Q5:. What certificate your company have?

A5: ISO 9001, ISO 14001, OHSAS 18001, CE, UL, IEC 61427 test report, Patent for gel technology and other Chinese honor.

Q6. What is your warranty time for VRLA battery ?

A6: It depends on battery capacity, depth of discharge, and battery usage. Please kindly contact us for accurate information based on detailed requirements.

Q7. Why battery has different capacity at different hour rate?

A7: The capacity of a battery, in Ahs, is a dynamic number that is dependent on the discharge current.
For example, a battery that is discharged at 10A will give you more capacity than a battery that is discharged at 100A.
With the 20-hr rate, the battery is able to deliver more Ahs than with the 2-hr rate because the 20-hr rate uses a lower discharge current than the 2-hr rate.

China 150ah 12v Lead Acidy Front Terminal Batteries Solar Panel Deep Cycle Sealed Agm supplier

150ah 12v Lead Acidy Front Terminal Batteries Solar Panel Deep Cycle Sealed Agm