Phase Angle Error CT PT Test Set

Brand Name:HNMC
Model Number:HEWE series
Minimum Order Quantity:1
Delivery Time:30-45 days
Payment Terms:L/C, T/T, Western Union
Place of Origin:China
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No.1207-1, Building #1, the National University Sci-Tech Park of Henan Province, No.11 Changchun Road, Zhengzhou, Henan 450000
Supplier`s last login times: within 38 hours
Product Details Company Profile
Product Details

Digital Transformer Tester HEWE series CT PT Test Equipment Comparator


Technical Parameter

Accuracy class2
Current range5A, 1A
Voltage range100V,100/√3V
Percentage ErrorLess than 1.5%*FS
Basic Error
When testing CT PT error & impedance & admittance, the error will not beyond:

ΔX=±(X*2%+Y*2%+Dx)

ΔY=±(X*2%+Y*2%+Dy)

ΔX: basic error limit value of in-phase component

ΔY: basic error limit value of Quadrature Component

X: Indication absolute value of in-phase component

Y: Indication absolute value of Quadrature Component

Dx & Dy: Zero error and Quantizing Error

When testing CT & PT, Dx,Dy=1(or 2)%*(Error limit value of CT & PT

When testing Z & Y, Dx,Dy= 3 digits


Measure Range & Resolution

CT PT classTest RangeResolution
In-phase componentQuadrature ComponentIn-phase componentQuadrature Component
0.01±0.4000±13.7520.0001%0.001'
0.02
0.05
0.1±4.000±137.520.001%0.01'
0.2
0.5
1.0±40.00±999.90.01%0.1'
Impedance Measure Range & Resolution
RangeMeasure Range (Ω)Resolution
5A±1.0000.0001
1A±6.0000.0001
Admittance Measure Range & Resolution
RangeMeasure Range (mS)Resolution
100V±9.99990.0001
57.7V±9.99990.0001

Features


1) LCD display

2) Test of ratio, ratio error, phase angle error, impedance, admittance

3) Test data values are all displayed

4) Used for testing of class 1 to 0.01 instrument transformer with rated current 5A and 1A,

rated voltage 100V, 100V√3V

5) Display ratio error & phase angle error of all test points under rated burden or lower limit

burden 1%-120% Rated current or 20%-120% rated voltage


Design for options

China Phase Angle Error CT PT Test Set supplier

Phase Angle Error CT PT Test Set