

Add to Cart
Partial Discharge Detector MCPD002
Technical Index
1. TEV measurement
Item | Specification |
Sensor | capacitance type |
Range | 0-60bBmV |
Frequency range | 3-100MHz |
Resolution | 1dB |
Accuracy | ±1dB |
Maximum impulse/cycles qty | 1400 |
Minimum impulse rate | 10Hz |
2. Ultrasonic Measurement
Item | Specification |
Range | -7dBuV~68dBuV |
Resolution | 1dB |
Accuracy | ±1dB |
Sensor sensitivity | -65dB (0dB=1V/ubar RMS SPL) |
Sensor center frequency | 40kHz |
Frequency range | 20~100kHz |
Sensor diameter | 16mm |
Heterodyne frequency | 38.4kHz |
3. HFCT measurement
Item | Specification |
Sensor type | HFCT |
Range | 0pC~25000pC |
Minimum impulse rate | 10Hz |
Frequency response | 100kHz~20MHz |
Inner diameter | 45mm(customization available) |
Outer diamete | 107 mm(customization available) |
Output impedance | 50Ω |
Output interface | BNC connector |
4. Temperature measurement
Item | Specification |
Sensor type | Infrared sensor |
Range | -20℃~150℃ |
Accuracy | ±1% or 1℃ |
Response wave length | 8~14um |
Distance coefficient | 15:1 |
Sending rate | 0.95 |
IP degree | 65 |
Humidity | 0~90% RD |
Size: | Φ20X90 |
5. Size & Weight: 240mm×125mm×60mm / 1.2kg
6. Rated input supply for charger: 90-264V AC/ 47-63HZ, charging voltage 12V DC