120V Protection Relay Test Equipment With Fault Playback

Brand Name:HNMC
Model Number:MCRT40
Minimum Order Quantity:1
Delivery Time:4-8weeks
Payment Terms:L/C, T/T, Western Union, MoneyGram
Place of Origin:China
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No.1207-1, Building #1, the National University Sci-Tech Park of Henan Province, No.11 Changchun Road, Zhengzhou, Henan 450000
Supplier`s last login times: within 38 hours
Product Details Company Profile
Product Details

Protection Relay Test Kit MCRT40


Main Functions


1) With 4 Phase voltage & 3 Phase current output, can test various of protection relay

2) 4th phase voltage Ux is multifunction voltage and can be set as 4 kinds of 3U0 or test testing synchronous

voltage, or any voltage value output.

3) Easy to operate with using rotation mouse and display by large LCD screen.

4) Can test all kinds of relay and micro-computer protections, also can simulate various complicated transient,

permanent&transformative fault to do whole group test

5) Can be operated by external PC, can test all kinds of object by software, also display vector diagram and

fault waveform, then can save the test records and print out.

6) Powerful software function: can finish various complicated test, such as three phase differential test,

line protection re-close test and etc…, and can test & scan various protection rated value, also can get

fault playback and real-time save test records, display vector diagram and then print out.

7) Switch signal:

7 circuits contact input and 2 pair idle contact output. Also this function can be extended

8) Large screen LCD display (320*240), with clear display.

9) With various protections inside, also with self-diagnose and interlock function.

10) With independent special DC power source output 110V&220V special-use adjustable DC source output.


Technical Index

AC current source
Output accuracy0.5%
Output range3*(0-40A); 0-120A (three phases in parallel)
Phase current which can get long-time working 10A
Maximum output power of phase current: 420VA
Maximum output power of three phase current in parallel: 900VA
Permissible working time (when three phase current in parallel to get maximum output): 10s
Frequency (basic wave) range20-1000Hz
Harmonics times1-20 times
DC current source
Output accuracy0.5%
Current output0-+/-10A per phase; 0-+/-30A (three phase in parallel)
Maximum load voltage output20V
Output accuracy0.5%
Phase voltage output4*(0-120V)
Line voltage output0-240V
Phase voltage/line voltage output power80VA/100VA
Frequency (basic wave) range20-1000H
Harmonics1-20 times
DC voltage source
Output accuracy0.5%
Phase voltage output amplitude0-+/-160V
Line voltage output amplitude0-+/-320V
Phase voltage/line voltage output power70VA/140VA
Dimension400*300*180mm
Weightapprox 20KG
Power supplyAC 220V±10%,50/60Hz
Ambient temperature-10℃ ~ +50℃

Switch signal and time measurement


Switch signal input

7circuits

Idle contact: 1~20mA,24V

Potential contact access: “0”:0~ +6V; “1”:+11 V~ +250V

Switch signal output2 pairsDC:220V/0.2A;AC:220V/0.5A
Time measure

Test range: 0.1ms ~ 9999s , accuracy 0.1mS

Measurement range: 0.1ms ~ 9999s

Measurement accuracy:0.1mS