Add to Cart
Negative Duct Air Rs485 Differential Pressure Sesnor Transmitter
Features Negative Duct Air Rs485 Differential Pressure Sesnor Transmitter
Fully intelligent circuit board, automatic compensation and linear
calibration, strong isolation of interference, to ensure signal
stability
It has reverse protection and current-limiting protection circuit.
When the positive and negative poles are reversed during
installation, the transmitter will not be damaged. When abnormal,
the transmitter will automatically limit the current within 35MA.
Soft wire, polyurethane wire, anti-corrosion, high and low
temperature resistance. The tail of the wire is sealed with a
polymer sieve, which can ensure the air permeability of the wire
and prevent water molecules from entering
The default is stable 0.25% accuracy, can be customized 0.1%
accuracy and higher
DescriptionNegative Duct Air Rs485 Differential Pressure Sesnor Transmitter
Parameter Negative Duct Air Rs485 Differential Pressure Sesnor Transmitter
Range: -10Kpa-0-10Kpa
Medium :Dry Air
Max.Static pressure: 70Kpa
Accuracy :±0.25%(Typical) ±0.5%(Max.)
Overload:20%FS
Long term stability:0.1%F.S/Y(≤2000KPa)
Temperature Drift:0.01%F.S/℃
Operating temperature range :-40℃~70℃
Storage temperature range: -40℃~70℃
Power supply:9~36VDC
Output signal :4~20mA /0-5V/0~10V//1~5V/RS485
Frequency response:less than 500Hz
Insulation resistance: 100MΩ,100VDC
Protection: IP54