APM-18 Stainless Steel Digital Aerosol Photometer For Hepa Filter

Brand Name:SUJING
Model Number:APM-18
Minimum Order Quantity:1
Delivery Time:5 work days
Payment Terms:T/T
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Suzhou Jiangsu China
Address: No.2 Weixin Road,Suzhou Industrial Park,Jiangsu,China
Supplier`s last login times: within 41 hours
Product Details Company Profile
Product Details

APM-18 Aerosol Photometer And Aerosol Generator For Hepa Filter


Aerosol Photometer is a kind of special test instrument to test the leakage of HEPA, designed on the base of light scattering principle, displays real-time leakage rate by detecting aerosol concentrations of upstream and downstream. Applicable for testing clean rooms, laminar flow benches, bio-safety cabinets, glove boxes, HEPA vacuum cleaners, HVAC systems, HEPA filters, ULPA filters, negative pressure filtration units, surgical suites, nuclear filter banks, collective protection filters, et


Features and Benefits of aerosol photometer

  • long life laser light source;
  • high precision photoelectric multiplier tube detection;
  • can set PAO, DOP and other types of aerosols;
  • equipped with a dedicated handheld device to achieve control, display and sampling function;
  • large capacity data storage, real-time data storage;
  • more than the setting alarm sound and light alarm;
  • can be obtained by U disk or thermal printer to print historical data;
  • can print leakage rate and other monitoring data in real time;
  • through the special software, the sampling data can be imported into PC;
  • automatic fault detection.

Application of digital aerosol photometer

  • leakage detection of clean room
  • VLF bench
  • biosafety cabinet
  • glove box
  • HEPA vacuum cleaner
  • HVAC system
  • HEPA filter
  • negative pressure filtering system
  • operating theatre
  • nuclear filter system
  • collection protect filter
APM-18 photometer Specifications
Dynamic RangeUp to 600 micrograms per liter
Reagent SettingsPAO-4, DOP, Ondina, Mineral Oil, Paraffin
Auto ZeroAutomatically establishes zero reading at startup
Sensitivity1% of readings ≥0.01% to 100%
Repeatability0.5% of readings ≥0.01% to 100%
Flow ControlPulse Width Modulation (PWM) control ensures sampling rate of 1cfm (28.3lpm) +/- 10% in all applications.
Light SourceSolid State, rated for life of instrument
ReportingContinuous, Summary, and Monitoring modes
AlarmUser selectable audible, visual, and vibratory alarms notify the user when the user defined set point is exceeded.
Size260 (W)X160(H)X360(D)
Weight10Kg
OutputWireless printer, USB interface
Power220VAC, 50/60HZ
Standards complianceNSF 49, IEST, ISO-14644


China APM-18 Stainless Steel Digital Aerosol Photometer For Hepa Filter supplier

APM-18 Stainless Steel Digital Aerosol Photometer For Hepa Filter