OBV5-C40
The surge arrestors OBV5-C40-LT meet the type 2 requirement class
according to IEC 61643-11. These devices protect low-voltage
consumer systems from overvoltages of all types and are available
in single-pole to four-pole versions. The use of high-performance
varistors permits a rapid response time and a low protection level,
without any line follow current. If circumstances are uncertain and
there is a risk of fire from an overload, the internal cut-off unit
disconnects the arrestor from the mains if necessary. In addition,
the QR code printed on the arrestor allows disary. In addition, the
QR code printed on the arrestor allows direct access to the online
installation instructions.
Technical Parameters
Model: OBV5-C40 | |||
Maximum continuous voltage AC | Uc | V | 275/320/385/440 |
SPD to EN 61643-11 | Type 2 | ||
SPD to IEC 61643-1 | class II | ||
Nominal discharge current (8/20< s) | In | kA | 20 |
Maximum discharge current (8/20< s) | Imax | kA | 40 |
Voltage protection level | Up | kV | < 1,3/1,5/1,8/2,0 |
Response time | tA | ns | < 25 |
Maximum back-up fuse | A | 125 | |
Temperature range | ϑ | ℃ | -40℃~+85℃ |
Protection rating | IP 20 | ||
Max. cable cross-section flexible (fine-wire) | mm² | 25 | |
Max. cable cross-section rigid (single wire/multi-wire) | mm² | 35 |
Feature&Benefits
1,Protect electric system and on-loading electrical apparatus from
thunder and instantaneous over-voltage.
2,Protect transmission of Ethernet signals with 48V DC / 34V AC
power supply circuits against
lightning induced surges.
3,Enhanced surge protection.
4,For mounting on 35mm DIN rails acc. to EN 60715.
5,It can effectively ensure the equipments work properly.
·Easy installation or retrofit.
·Din-rail mountable.
·Fail-safe /self-protected designRemote indicator (optional) with
3pin NO/NC contact.
·IP20 finger-safe designVisual indicator.
·Small foot print.
Application
●AC/DC distribution
●Power supplies
●Industrial automation
●Telecommunications
●Motor controls systems
●PLC applications
●Power transfer equipment
●HVAC applications
● AC drives
●UPS systems
●Security systems
●IT/Data centers
Lightning protection grounding
It is not only a systematic project but also a dangerous project.
Direct lightning strikes have direct damage to the human body,
while induced lightning will cause a huge impact on the equipment
and damage the equipment in the equipment room. Therefore, it is
not only good to understand the basic knowledge of lightning
protection and grounding. The protective equipment room can better
protect the personal safety of employees.
1. The use type and function of the arrester:
The commonly used surge arresters are valve type, exhaust type,
zinc oxide, etc. The lightning arrester is used to protect the
lightning overvoltage from intruding into the substation or other
buildings along the line so as not to endanger the insulation of
the protected object. Nowadays, zinc oxide surge arresters are
often used outdoors in the power distribution, and valve arresters
are generally used indoors.
2. The concept of safe current:
Safe current refers to the maximum current that the human body can
get rid of after an electric shock. The safety current lightning
protection device stipulated in our country is 30 mA. The safety
current is related to factors such as the time of electric shock,
the nature of the current, the path of the current, and the weight
and health status.
3.The concept of safe voltage:
An area voltage refers to a voltage that does not directly cause
death or disability. The safety extra-low voltage specified in our
country is 36 volts.
4.The concept of land:
Electrical ground refers to a place where the potential is zero;
this ground generally refers to a place about 20 meters away from
the ground fault point.
5. The concept of working grounding and protective grounding:
The grounding to ensure that the power system and equipment meet
the requirements of normal operation is called working grounding.
The grounding to protect personal safety from contact with
electricity is called protective grounding. For example: the
neutral point of the transformer is grounded, and the grounding of
the lightning arrester and the lightning arrester is the working
ground. The grounding of the secondary side terminal of the
transformer and the grounding of the equipment surge protector
shell are the protective grounding.
Others
Technology SPD parameter(Note:According to user requirement ,can be
customized Uc=140V,440V,550V,voltage range of range of the SPD):
Type No. | Rated Voltage(V) Un | Continuous Voltage Uc(V~) | Standard Discharge Current In(KA) | Max Discharge Current | Protection Level(KA~) | Response Time(ns) |
DGM1(2)-D5 | 220/380 | 275/320 | 5 | 10 | 1.2 | ≤25 |
DGM1(2)-D10 | 10 | 2 | 1.6 | |||
DGM1(2)-C20 | 20 | 40 | 1.8 | |||
DGM13-B30 | 30 | 60 | .2.2 | |||
DGM3(4)-B40 | 10 | 80 | 2.4 | |||
DGM(4)-B60 | 60 | 100 | 2.8 | |||
DGM-N-PE | 220/255 | 40/60 | 60/80 | 1.2 | ≤100 |
Transient voltage surgesin lv power lines
Transient overvoltages are voltage surges that can reach tens
ofkilovolts with a duration of the order of microseconds.Despite
theirshort duration, the high energy content can cause serious
problemsto equipment connected to the line, from premature aging to
destruction, causing disruptions to service and financial
loss.Thistype of surge can have various different causes, including
atmospheric lightning directly striking the external
protection(lightning rods) on a building or transmission line or
the associatedinduction of electromagnetic fields on metallic
conductors.
Outdoor and longer lines are the most exposed to these fields,which
often receive high levels of induction.
It is also common for non-weather phenomena, such as transformer
centre switching or the disconnection of motors orother inductive
loads to cause voltage spikes in adjacent lines.
Importance of theground connection
Overvoltage protectors (SPD) divert excess energy toground, so
limiting the peak voltage to an acceptablevalue for connected
electrical equipment.
A ground connection in adequate condition is, therefore,a key
aspect for effective protection against overvoltages.Monitoring
ground connection condition guaranteesproper operation of surge
protection devices.
Q: Can I get some samples?
A: Yes, Sample orders welcomed.
Q: Can I use my own Logo or design on goods?
A: Yes, Customized logo and design on mass production are
available.
Q:What is the delivery time?
A: 3 days for samples, 7-15 days for mass production.
Q: What is the payment term?
A: T/T, L/C at sight, West union , Paypal, etc.