3 Phase 10KVA 8KW Online UPS Systems With External Battery Backup
Industrial Special-purpose Online UPS 10KVA 8KW Three Phase Ups With External Battery
High-reliability Industrial Grade Design:
The ZGD310 system is composed of power special-purpose UPS, DBW
regulator cabinet, PDU series feeder cabinet. CONSNANT Company
apply herself to the development of China’s electricity demands for
power plants, substations, power distribution products are designed
with online double conversion, zero conversion function. Main
applications including electric power long distance, RTU, power
carrier wave, power monitoring and so on. When the utility power is
normal, single phase 220V(or three phase 380V.) After isolation,
rectification and filtering through the inverter to provide a
stable power supply to the load; if the input AC power is abnormal
or power failure, the backup power system by the DC screen provide
power through non-return diode inverter. When the DC screen occurs
voltage shortage or power break, the static switch transfer to
bypass for power supply; when the electricity is restored, the
inverter automatically switches to utility power and provide power
supply under inverter mode. If the inverter overload or fault and
transfer power supply under bypass mode, also give a warning signal
at the same time.
Application:
Petroleum, chemical industry, gas and power station and so on.
Key features:
Adopt full digital control technology
Intelligent detection and monitoring function
Digitally control the static switch with zero switch
Full isolation between input and output
Super low output zero earth voltage
DC UPS isolated with utility power completely
Cubical design with power standard (customization)
Multifunctional protection for overvoltage, under voltage, over
current, short circuit and over temperature and so on.
Large-screen LCD monitor with Chinese and English operation
interface
Ultralong 256 event record, user-friendly analysis and management
to the situation of the power supply (touch screen optional)
Static bypass has a strong anti-overload capability
Control system
It adopts microprocessor bus control technology, three core
processor controlling rectification, inversion and parallel
connection respectively, to ensure the real-time control of the
rectifier, inverter and static switch and the coordination of every
power part, characterized by increased control of aging, higher
reliability, enhance of the efficiency of the whole UPS system and
the output technical parameters are better than that of the device
with same capacity.
Model Papacity(KVA) | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | |
Capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW | |
lnput | |||||||||
Rated voltage | 400 Vac three-phase | ||||||||
Voltage range | ±20% | ||||||||
Frequency range | 50/60HZ±5% | ||||||||
Power factor | ≥0.8 | ||||||||
Current harmonic distortion | <5%with harmonic filter | ||||||||
Soft Start | 0-100% in10" | ||||||||
Bypass Input | |||||||||
Rated voltage | 230Vac single-phase | ||||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | ||||||||
Rated frequency | 50/60Hz | ||||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | ||||||||
Standard features | BackFeed portection; split bypass line | ||||||||
Batteries | |||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | ||||||||
Maximum recharge current(A) | 0.2 X C10 | ||||||||
DC Voltage | 384VDC | 432VDC | |||||||
AC ripple voltage | <1% | ||||||||
Inverter output | |||||||||
Number of phases | 1 | ||||||||
Rated voltage(V) | 230Vac single-phase | ||||||||
Regulation of the output voltage | 220÷244Vac phase/neutral(from contril panel) | ||||||||
Crest factor(Ipeak/Irms) | 3:1 | ||||||||
Static stability | ±1% | ||||||||
Dynamic stability | ±5% | ||||||||
Frequency | 50/60Hz configurable | ||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | ||||||||
Frequency stability | ±0.05% on mains failure | ||||||||
System | |||||||||
Remote signaling | Volt free contacts | ||||||||
Remote controls | EPO and Bypass | ||||||||
Communication | RS232 + romote contacts | ||||||||
Operation temperature | 0℃/ + 40℃ | ||||||||
Relative humidity | <95% non condensing | ||||||||
Colour | Light grey (RAL 7035) | ||||||||
Noise | 54dBA at 1m | 60dBA at 1m | 65dBA at 1m | ||||||
Protection degree | IP42 | ||||||||
Efficiency Smart Mode | up to 98% | ||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) | ||||||||
Weight(KG)N.W | 200 | 220 | 230 | 290 | 340 | 440 | |||
Dimensions:(WxDxH)mm | 600*800*1900 |