Local Area Network 30KVA Low Frequency Online UPS 3 Phases 380V / 400V / 415V

Brand Name:ZGD
Certification:CE
Minimum Order Quantity:1 sets
Place of Origin:China
Rated Voltage:380/400/415 Vac three-phase
Frequency Range:45-65Hz
Contact Now

Add to Cart

Active Member
Location: Shenzhen China
Address: 708, No.218, Changchun Road, Shangcun Community, Gongming Street, Guangming District, Shenzhen
Supplier`s last login times: within 25 hours
Product Details Company Profile
Product Details

30KVA UPS Low Frequency Online UPS 3 Phases UPS 380V/400V/415V 30 Kva Ups

Advance communication
Compatible with TeleNetGuard for remote maintenance; Advanced, multi-platform communication for all operation systems and network environments: Watch & Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 2008, Vista,2003, XP; Mac OS X, Linux, Novell and most popular Unix operating systems;

The UPS is supplied with a cable for direct connection to the PC(Plug and Play); RS232 double Serial port; Installation slot for an Emergency Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency; Generator interface: enables resynchronization of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge.

Expandability:
The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.


Model powerZGD330 10-200KVA
10KVA15KVA20KVA30KVA40KVA60KVA80KVA100KVA120KVA160KVA200KVA
Capacity8KW12 KW16 KW24 KW32 KW48 KW64 KW80 KW96KW128 KW160 KW
Input
Rated voltage380/400/415 Vac three-phase
Voltage range±20%
Frequency range45-65Hz
Power factor>0.92with harmonic filter
Current harmonic distortion<5%with harmonic filter
Soft Start0-100% in10"
Bypass Input
Rated voltage380/400/415 Vac three-phase
Permitted voltage range±15%(selectable from ±10% to ±25% from front panel)
Rated frequency50/60Hz
Permitted frequency range±2%(selectable from ±1% to ±5% from front panel)
Standard featuresBack Feed protection; split bypass line
Batteries
TypeMaintenance-free lead-acid VRLA AGM / GEL;NICd
Battery voltage384VDC480VDC
Maximum recharge current(A)0.2×C10
AC ripple voltage<1%
Inverter Output
Number of phases3+N
Rated voltage(V)380Vac
Regulation of the output voltage380~424Vac phase/neutral(from control panel)
Crest factor (Ipeak / Irms)3:1
Static stability±1%
Dynamic stability±5%
Frequency50/60Hz configurable
Overload110% 125% 150% of the rated current for 5h/10'/1'
Frequency stability±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present
Remote signalingVolt free contacts
Remote controlsEPO and Bypass
CommunicationRS232 + romote contacts
Operation temperature0ºC/ + 40ºC
Relative humidity<95% non condensing
Noise54dBA at 1m50-65dBA at 1m
Protection degreeIP20
Efficiency smart modeup to 98%
ComplianceSafety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)

China Local Area Network 30KVA Low Frequency Online UPS 3 Phases 380V / 400V / 415V supplier

Local Area Network 30KVA Low Frequency Online UPS 3 Phases 380V / 400V / 415V

Inquiry Cart 0