Product Details Company Profile
Product Details

S14-M Oil Iron Core Transformer 1600KVA Electric Power Transformer

S11/S13/14-M Oil-Immersed Transformer ISO IEC GB 10KV 30-1600KVA 50Hz oil type iron core


Product Introduction


Product Standards

GB1094.1-2013 General rules for power transformers
GB1094.2-2013 Power Transformer Temperature Rise
GB1094.3-2003 Insulation Level and Insulation Test of Power Transformers
GB1094.5-2008 Power transformer withstands short circuit capability
GB/T1094.10-2003 Power transformers - Part 10: Determination of sound levels
GB/T25446-2010 Oil-immersed amorphous alloy core distribution transformer technical parameters and requirements


Conditions

1. Conditions of the normal environment: The altitude does not exceed 1000m;
2. The highest ambient temperature +40 °C, the lowest -25 °C;
3. Conditions for special environments: Altitude over 1000m;
4. The highest ambient temperature +40 °C, the lowest -45 °C. (Detailed description when ordering);
5. Installation site: no corrosive gas, no obvious dirt environment;
Note: According to the agreed conditions, to provide users with products under special conditions of use.


10KV-S11 Oil Transformer main technical data

Rated Capacity
(KVA)
High
voltage
(KV)
Tapping
Range
Low
voltage
(KV)
Frequency
(Hz)
Connection
Symbol
No-load loss
(W)
load loss
(W)
No-load Current
(%)
Noise level
(dB)
Short-circuit
impedance (%)
Gauge
A x B
(mm x mm)
Dimensions
L*W*H (mm)
Weight (KG)
306
6.3
6.6
10
10.5
11
±5%
±2X 2. 5%
0.450
  1. yn11
  2. Y, ynO
1006302.3444400770X545X890260
501309102.044400790X560X920320
8018013101.948400850X635X980420
10020015801.848550865X685X990470
16028023101.6495501120X740X1050610
20034027301.5515501235X825X1080750
25040032001.4515501275X860X1100850
31548038301.4535501300X870X1170960
40057045201.3536601395X960X11901160
50068054101.2546601530X1080X12301340
63081062001.1544.56601660X1180X13001660
80098075001.0578201740X1255X14002100
10001150103001.0578201780X1320X14902400
12501360120000.9598201855X1345X15802850
16001640145000.8598201960X1415X17003430

10KV-S13/14 Oil Transformer main technical data

Rated Capacity
(KVA)
High
voltage
(KV)
Tapping
Range
Low
voltage
(KV)
Frequency
(Hz)
Connection
Symbol
No-load loss
(W)
load loss
(W)
No-load Current
(%)
Noise level
(dB)
Short-circuit
impedance (%)
Gauge
A x B
(mm x mm)

Dimensions

L*W*H (mm)

Weight (KG)
S13S14S13S14
30

6

6.3

6.6

10

10.5

11

±5%

±2X 2.5%

0.450D, yn11 Y. ynO8080630/600505/4801.4504400X40C1005X670X960280
50100100910/870730/6951.250400 X 40C1005X670X990390
801301301310/12501050/10000.9752400X40C1060 X 715X1040495
1001501501580/15001265/12000.9752550X55C1075X735X1060600
1251701701890/18001510/14400.8454550X55C1110X750X1100690
1602002002310/22001850/17600.8454550X55C1140X780X1130780
2002402402730/26002185/20800.7456550X55C1210X815X1150908
2502902903200/3052560/24400.6456550X55C1290X885X11901043
3153403403830/36503065/29200.6458550X55C1300X880X12301190
4004104104520/43003615/34400.5458660 X 66C1410X975X13001430
5004804805410/51504330/41200.5460660X66C1465 X 980X13901648
630570570620049600.54604.5660X66C1560X1050X14102027
800700700750060000.4862820X82C1700X1160X14802500
10008308301030082400.4262820X82C1790X1280X15202700
12509709701200096000.3665820X82C1890X1360X16003280
16001170117014500116000.3669820X82C1970X1430X1700

3500


Structural Features

Iron core: The magnetic material of iron core uses amorphous alloy. Since the amorphous alloy does not have a crystal structure and has a soft magnetic characteristic, the area of ​​the hysteresis loop is very narrow, the magnetization
power is small, the electrical resistivity is high, and the eddy current loss is small, so the no-load loss and no-load current of the transformer made of this material are used. very low. The core is composed of four separate core frames in the same plane
to form a three-phase five-column type. It must be annealed, and it must have a cross-barrier joint with a rectangular cross-sectional shape.

Coil: In addition to using low-voltage windings (160kVA or less) with copper conductors, a cylindrical structure made of copper foil is generally used; high-voltage windings use a multi-layered cylindrical structure to balance the winding ampere distribution and magnetic flux leakage. High-voltage and low-voltage windings are wound together with wire tension devices to form rectangular coils, and the coils are solidified by hot-pressing and shaping to enhance the mechanical strength of the windings and the ability to withstand short circuit.

Oil tank: It adopts a beautiful full-sealing and maintenance-free corrugated structure. Through advanced oil tank production technology,it undergoes strict pressure...