KNKONG JP-400 LV Meter Distribution Box IEC439-1
Product Introduction
JP low-voltage integrated distribution box shall comply with IEC439-1 "Low-voltage switchgear and control equipment", GB7251.12-2013 "Low-voltage switchgear and control equipment Part 2: Complete power switch and control equipment", GB/T15576- 2008 "Low-Voltage Complete Reactive Power Compensation Device" related standard requirements.
Service environment
1. Air temperature: -25℃---+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity
90%.
3. Altitude: ≤ 2500m
4. Ambient air not apparently polluted by corrosive and flammable
gas, vapor, etc.
5. No frequent violent shake
Main Parameter
NO. | Description | Unit | Parameter |
1 | Rated voltage | V | 400 |
2 | Rated frequency | HZ | 50 |
3 | Capacity | KVA | 30 50 63 80 100 125 160 200 250 315 400 500 630 |
4 | Capacitor grouping | 2 3 4 5 levels (according to user requirements ) | |
5 | Bus bar Rating | A | 630 |
6 | The metal used for busbars | Copper | |
7 | Type of protection used on busbars against corrosion (e.g. heavily tinned) | Tinned Plating | |
8 | Dimens ions of busbars (length x width x thickness) | mm | 660 x 50x 5 |
9 | Method of connection between busbars and cable lugs (cable lugs not to be provided) | Bolted Typ e | |
10 | Fixing center of HRC fuse | mm | 90 |
11 | Ar e-safety barriers fitted between phases of the same incoming or outgoing unit? | Yes | |
12 | Are insulating shields fitted between adjacent units? | No | |
13 | Minimum clearance between the lowes t cable connection and ground level | mm | 300 |
14 | Material used for housing | Ho t Dipped Galvanized Sheet | |
15 | Treatment of housing against atmospheric corrosion | 7 Tank Process | |
16 | Padlocking facility on housing door | Yes |