Interlocked Fuse Protection Gas Insulated Switchgear RMU

Brand Name:Knkong
Certification:IEC ISO GB
Model Number:SF6 GIS HXGN15-12 Fuse protection unit
Minimum Order Quantity:1
Delivery Time:30 days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China
Supplier`s last login times: within 11 hours
Product Details Company Profile
Product Details

GB ISO 12KV Gas Insulated Switchgear Medium Voltage Ring Main Unit

Product Introduction


General

The Fuse switch which named F-unit is a double-position load switch with an independent grounding switch, the tripping
device and the load switch farms the load switch-fuse combination.
The Grounding switch uses double mode, which can be grounded on both sides of the fuse at the same time, thus it ensures
that the fused fuse is not charged other the earthing switch is closed. Double grounding switch is interlocked mechanically, and primary ground operates grounding of two earthing switches of the same time.
The front cover of the fuse compartment is also mechanically interlocked with the earthing switch, and only when it is founded,
the fuse can be contacted.

Service environment

  • Air temperature: -35℃~+40℃
  • Humidity: Monthly average 95%; Daily average 90%.
  • Altitude:≤ 1000m (Up to 5000 m can be custom)
  • Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
  • No frequent violent shake

Technical Data

No.ItemUnitParameter
1Rated voltagekV122436
2Rated frequencyHz50/60
3Rated currentA630(1250*)
4

1min Power frequency

withstand voltage

wetkV385070
drykV486085
5Lightning impulse withstand voltagekV75125/150170
6Rated short circuit breaking current (peak)kA806363
7Rated active load and close circuit breaking currentA635050
8Rated transferring currentA170012001200
9Rated short circuit making a current (peak)kA806363
10Rated cable(line) charging breaking currentA

50 and 10

50/10

11Cable charge breaking current in earthing faultA202020
12Rated withstand current (peak)kA806363
13Short-time withstand current (2s)kA252020
14Mechanism lifetimes500020002000

Note: For short circuit breaking and the peak current is based on Fuse plus combination


Optional components:
Electric operating-AC 220/110V; DC 24/48/110/220V
Auxiliary contact 5 NO 5 NC
Full set of fuse
FTU communication interface



China Interlocked Fuse Protection Gas Insulated Switchgear RMU supplier

Interlocked Fuse Protection Gas Insulated Switchgear RMU

Inquiry Cart 0