Solid Sealed Pole Vacuum VCB Circuit Breaker 12KV For Transformer Substation

Brand Name:KNKONG
Certification:CB,ISO,IEC
Model Number:VS1-12
Minimum Order Quantity:1
Delivery Time:15 working days
Payment Terms:L/C, T/T, Western Union
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China
Supplier`s last login times: within 11 hours
Product Details Company Profile
Product Details

VCB solid-sealed pole vacuum circuit breaker 2000A 12KV for transformer substation using

Voltage: 12-24KV

Current: Max 2000A

Breaking current: 20KA

Type: withdrawable/Fixed


Product overview

VS1-series solid-sealed pole vacuum circuit breaker is suitable for 12kV, 24KV, three-phase alternating current frequency of 50, 60Hz indoor switchgear KYN28-12 (24) central and fixed switchgear operation together. The VS1 vacuum circuit breaker can be fixedly installed or combined with a trolley.


Special service condition

The special operating conditions are negotiated in advance by the manufacturer and the user (the manufacturer must consult the user in advance for each special operating condition) such as:
-Whether the site altitude exceeds 1000m (or need to order a prototype circuit breaker).
-Allows reducing the dielectric strength of the air.
-Corresponding insulation requirements.
-Situations where the ambient temperature rises.
-Whether the current carrying capacity is reduced.
-Is it necessary to provide additional ventilation for heat dissipation
Other precautions should be negotiated with the manufacturer according to section 2.2 of IEC 62271-1

Technical Parameters

No.ItemUnitParameter
1Rated voltageKV12
2Rated frequencyHz50/60
3

Rated insulation level

1min power frequency withstand voltage(r. m. s)

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)


4


Rated current


A

63063012501600
1250125016002000
20002500
25003150
4000
5Rated short-circuit breaking current

KA

202531.540
6Rated short-time withstand current202531.540
7Rated short-circuit marking current506380100
8Rated peak withstand current506380100
9Rated duration of short-circuits4
10Rated operating sequenceO-0.3s-O/C-180s-O/C
11Breaking times of rated short-circuit currentTimes30/20 times(40KA)
12Mechanical enduranceOps20000
13Rated single capacitor bank breaking current

A

630
14Rated back-to-back capacitor bank breaking current400
15Double-earth fault breaking current27.4
16Allowable maximum contact erosion

mm

3
17Clearance between open contacts10±1
18Over stroke3.5±0.5
19Non-simultaneity of 3-phase opening and closing

ms


≤2
20Bounce duration of contact closing≤2
21Average breaking speed (instant breaking 6mm)

m/s


1.1±0.2
22Average making speed0.8±0.2
23Making time

ms


≤100
24Breaking time≤50

25


Resistance of each phase main circuit


μ Ω

630A≤50
1250A≤45
1600A~2000A≤35
≥2500A≤25
26Contact breaking bounce amplitudemm≤2

27

Rated operating voltageRated operating voltage(V)AC/DC

V

24*110220
Scope of normal operation voltageOpening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28Rated voltage of energy storage motorVAC110/220,DC110/220
29Energy storage timeS≤15

Operation safety

VS1 vacuum circuit breaker has anti-misoperation lockout protection, realizes the "five guarantee" interlock function in the switch cabinet, avoids misoperation, and protects the personal safety of operators to the greatest extent.
Only when the VS1 vacuum circuit breaker and the grounding switch are in the off position at the same time, can the trolley roll from the "detection position" to the "service position".
The VS1 vacuum circuit breaker can only be closed in the "service/test" position.
When the VS1 vacuum circuit breaker is closed, the trolley cannot be moved in or out, only when the circuit breaker is in the off position.
The VS1 vacuum circuit breaker in the closed position cannot be shaken out from the "service position" to the "detection position".
The circuit breaker cannot be closed when pushed in.
When the circuit breaker is closed, if the closing signal is not released in time, the internal anti-trip control circuit will cut off the closing circuit to prevent multiple reclosing (optional).
Note: If the customer chooses electric closing and locking instead of manual closing and locking, the circuit breaker will not be closed when the secondary circuit cannot provide power or the power provided cannot meet the normal operation of the locking electromagnet (optional).