IEC Medium Voltage Switchgear 630A 36KV Metal Clad Panel

Brand Name:KNKONG
Certification:CB,ISO
Model Number:KYN61A-40.5KV
Minimum Order Quantity:1
Delivery Time:15 working days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Active Member
Location: Zhengzhou Henan China
Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China
Supplier`s last login times: within 11 hours
Product Details Company Profile
Product Details
36KV metal clad panel KYN61 type switchgear 2000A 1600A 1250A 630A
KYN61 switchgear,
Knkong,ABB or Schneider inside
40.5KV, 3-phase, AC 50/60Hz
Standard IEC GB
Design switchgear plan as SLD (Single Line Drawing)

Product Introduction

This product complies with: GB3906 "3-35kV AC Metal-enclosed Switchgear", GB/TII022 "High Voltage Switchgear and Control Equipment Standard Common Technical Requirements", DL/T404 "AC High Voltage Switchgear Ordering Technical Conditions", IEC60298 "Rated Voltage 1kV above 52kV and below AC metal-enclosed switchgear and control equipment" standard.

Technical data

ItemsUnitData
Rated VoltageKV40.5
Rated FrequencyHz50
Rated CurrentA1250,1600,2000
Rated Short-circuit Breaking CurrentKA25,31.5
Rated Making Current (Peak)KA63,80
4s Thermal Stability CurrentKA25,31.5
Rated Dynamic Current (Peak)KA63,80
Rated Insulation Level1min Power Frequency Withstand Voltage (r.m.s)KV95
Lightning Impulse Withstand Voltage (Peak)KV185
1min Power Frequency Voltage Across the open gap (r.m.s)KV118
Lightning Impulse Withstand Voltage Across the open gap (Peak)KV215
Enclosure Protection Class

Enclosure IP4X,

Between Compartments IP2X

Enclosure Dimension (Width*Depth*Height)mm1400*2800*2600
1600*2800*2600
Type of Circuit BreakerVCB:ZN85-40.5
SF6 Circuit Breaker

*Note: order switchgear should provide SLD(Single-line diagram) by customer


VS1-40.5 Technical data

ItemsUnitDate
Rated voltage

KV

40.5
Rated short-time power frequency withstand voltage (1min)95
Rated lightning impulse withstand voltage (peak)185
Rated freqHz50/60
Rated currentA1250 1600 2000 2500 4000
Rated short-circuit drop-out currentKA25 31.5
Rated short time withstand current25 31.5
Rated short time continual times4
Rated peak withstand currentKA63 80
Rated short-circuit closing current63 80
Rated single/ back-to-back capacitor bank drop-out currentA630/400
Opening time (rated volt.)ms35~60
Closing time (rated volt.)50~100
Mechanical lifetimes20000
Rated break times for rated short drop out currents20
Rated operation voltageVAC110/220 DC110/220
Rated current of power storing motorW230
Average opening speedm/s1.6~2.0
Average closing speed0.5~0.8
Rated operation procedure

opening-0.3s-closing

opening-180s-closing opening


China IEC Medium Voltage Switchgear 630A 36KV Metal Clad Panel supplier

IEC Medium Voltage Switchgear 630A 36KV Metal Clad Panel

Inquiry Cart 0