6 X Self Regulating Heat Trace Cable For Process Temperature Maintenance

Brand Name:MICH
Certification:ISO9001
Model Number:HTMIHCPTM
Minimum Order Quantity:1 meter
Delivery Time:in one month
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Address: 1200 N Fuxing Rd Wutong Dist Tongxiang 314500 Zhejiang P. R China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

Electric Heat Trace Cable and Element for Process Temperature Maintenance is a special purposed heat trace cable and controls as an industrial process temperature maintenance system, which can maintain the temperature of the fluid in a pipe to the desired level, over a broad range of temperatures, depending on the need dictated by the particular process or application.


Heat Trace Mineral Insulated Heating Cable can meet the needs of high temperature condition and heat tracing of long-distance transportation pipeline. The maximum withstand temperature of the copper sheathed heating cable (MICU) provided by MICH can reach up to 250℃. Conductor resistance value ranges from 1.7-2000Ω/km. For the occasion of anti-corrosion or buried application, high density polyethylene (HDPE) outer sheath ( cable known as MIHC) is needed to be added. MIHC’s withstanding maximum temperature can be up to 90℃. Mineral insulated heating cable possesses excellent mechanical strength. The heating cable of series resistance provided by MICH can meet the requirements of different power levels.


High-temperature heat pipes are typically defined as heat pipes that operate between 400 and 1100°C. However, the fluid properties vary too much across this wide temperature range for any one of those fluids. Three fluids are typically used to cover this range; Cesium, Potassium, and Sodium. The operating range for each fluid is shown below:


Cesium 300 to 600°C (572 to 1,112°F)

Potassium 400 to 1000°C (752 to 1,832°F)

Sodium 500 to 1100°C (932 to 2,012°F)


Typical applications for high-temperature heat pipes include the following:


1. Heat Engine Receivers (Steam, Stirling, Brayton, Rankine)

2. Solar Thermal

3. Heat exchangers

4. Hypersonic wing leading edges

5. Waste heat recovery

6. Nuclear power

7. Thermoelectric Generators

8. Isothermalizing furnace elements


Cable Structure


Specification

Heating cable instruction code


MI CU-B 16K320/60/2520/220/E1

No. 1 2 3 4 5 6 7


No.Instruction
1Sheath materialCU
2structure of cable componentsshown in table 1
3cable codesshown in table 2, 3 and 4
4length of heating cableIn meter
5Heating cable powerIn Watt
6heating cable voltageIn Volt
7heating cable voltageSee table 5

Cable Code


1 6 K 320

No. 1 2 3 4


Serial NO.Instruction
1core number1 or 2
2Voltage grade3=300V, 6=600V
3conductor materialsC,K
4cold resistance ×1000320=0.32Ω/m×1000

Table 1 Structure of Cable Element


Note: Model C, F and G are suitable for being used at temperature under 65


Table 2 Heating Cable Specification (600V Single Conductor)


Cable CodeDiameterHDPE DiameterStandard resistance value at +20Maximum Production LengthUnit weight
mmmmΩ/mmkg/km
16C1.78.2100.0017350366.54
16C2.27.69.40.0022380307.77
16C2.97.08.80.0029400264.45
16C45.97.70.004600190.88
16C75.37.10.007600154.08
16C114.96.70.011600132.25
16C134.66.40.013600 (300)☆125.7
16C174.66.40.017600 (300)☆117.16
16C214.66.40.021600 (300)☆111.9
16C253.75.50.025600 (480)☆68.83
16C333.75.50.033600 (480)☆63.76
16C403.45.20.04600 (560)☆58.87
16C633.250.06360051.47
16K806.88.60.08370 (140)☆254.18
16K1005.270.1450 (240)☆162.11
16K1404.96.70.14600 (270)☆122.55
16K1974.456.250.197600 (330)☆111.32
16K2204.56.30.22600 (330)☆102.89
16K3154.36.10.315600 (350)☆91.44
16K3454.26.00.345600 (370)☆85.9
16K4504.05.80.45600 (400)☆80.73
16K6304.05.80.63600 (400)☆77.26
16K8003.55.30.8600 (530)☆61.48
16K12502.84.61.2560040.83
16K20002.84.62.060038.96

Table 3 Heating Cable Specification (600V Double Conductors)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26C3.412.90.0034150783.76
26C4.412.20.0044160701.56
26C5.811.30.0058170606.16
26C8.69.900.0086180451.43
26C11.49.300.0114200400.05
26C13.89.000.0138210375.20
26C17.28.600.0172220344.90
26C238.000.023250303.25
26C34.47.500.0344280269.20
26C49.27.100.0492300243.84
26K2409.900.24180451.43
26K3209.300.32200400.05
26K3849.000.384210375.20
26K4808.600.48220344.90
26K6408.000.64250303.25
26K9607.500.96280269.20

Table 4 Heating Cable Specification (300V Double Cores)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23C3.412.00.0034200708.10
23C4.411.30.0044220629.07
23C5.810.40.0058240537.73
23C8.69.000.0086260392.56
23C11.48.400.0114280343.89
23C13.88.000.0138300314.57
23C17.27.600.0172320286.27
23C237.100.023340252.98
23C34.46.600.0344360221.19
23C49.26.200.0492380197.64
23K16010.40.16220508.37
23K2409.000.24240392.56
23K3208.400.32265343.89
23K3848.000.384280314.57
23K4807.700.48300291.91
23K6407.100.64320252.98
23K9606.500.96350216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH


Table 5 terminal specifications


Model: A, D, EModel: B
Maximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)
60015E220E115E1
60020E225E220E1
60030E340E230E2
60050E370E250E2
60070E3100E370E2

Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.

Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.


Corresponding reference table between the output power and sheath temperature


Note: when applying a copper conductor heating cable, please pay attention to the conversion of its heated hot resistance and unheated cold resistance.


Anticorrosive specification


Material

MICU

MIHC
SulfateNot recommendExcellent
Hydrochloric acidNot recommendExcellent
Hydrofluoric acidAcceptableAcceptable
PhosphateAcceptableAcceptable
CarbonateNot recommendAcceptable
Organic acidAcceptableNot recommend
Alkali metalAcceptableAcceptable
Sea waterNot recommendAcceptable
ChlorideData checking requiredAcceptable

Explosion-proof instructions


MIAL series heating cable with explosion-proof terminal, can be used in potential explosive environment. Authenticated by the Chinese CQST, in accordance with Chinese GB3836 explosion-proof electrical standards, they can be applicable to A, B, Ⅱ C (C1D2) level of explosion-proof electrical equipment.