Mineral Insulated Electrical Tracing On Pipe

Brand Name:MICH
Certification:ISO9001
Model Number:MIHTPVPPPCPI
Minimum Order Quantity:1 meter
Delivery Time:in one month
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Address: 1200 N Fuxing Rd Wutong Dist Tongxiang 314500 Zhejiang P. R China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

Mineral Insulated Heat Trace to Pistons, Valves, Pumps, Pipes, Pipe bends and Containers for Pharmaceutical Industry are used on the heat trace for the vessels like piston, valve, pump, pipe, bend and containers where the viscous media are stored and transported. Generally speaking, during normal production, electric heat tracing does not work. Only when the equipment is not running, the electric heat tracing system is turned on to ensure that the equipment can work normally when it is restarted.


MI armoured heating cable is made of single or multiple alloy electric heating wire as heating source, insulated with high purity, high temperature, electric melting crystallization magnesium oxide, sheathed by seamless continuous stainless steel or copper tube and formed using special production process. Used in highly corrosive places, PE or low smoke halogen-free coat can be added.


This heat tracing solution is suitable for explosion-proof, anti-corrosion areas, with the advantages of cost saving, environmental protection, easy installation and long service life etc.


Cable Structure


Specification

Heating cable instruction code


MI CU-B 16K320/60/2520/220/E1

No. 1 2 3 4 5 6 7


No.Instruction
1Sheath materialCU
2structure of cable componentsshown in table 1
3cable codesshown in table 2, 3 and 4
4length of heating cableIn meter
5Heating cable powerIn Watt
6heating cable voltageIn Volt
7heating cable voltageSee table 5

Cable Code


1 6 K 320

No. 1 2 3 4


Serial NO.Instruction
1core number1 or 2
2Voltage grade3=300V, 6=600V
3conductor materialsC,K
4cold resistance ×1000320=0.32Ω/m×1000

Table 1 Structure of Cable Element


Note: Model C, F and G are suitable for being used at temperature under 65


Table 2 Heating Cable Specification (600V Single Conductor)


Cable CodeDiameterHDPE DiameterStandard resistance value at +20Maximum Production LengthUnit weight
mmmmΩ/mmkg/km
16C1.78.2100.0017350366.54
16C2.27.69.40.0022380307.77
16C2.97.08.80.0029400264.45
16C45.97.70.004600190.88
16C75.37.10.007600154.08
16C114.96.70.011600132.25
16C134.66.40.013600 (300)☆125.7
16C174.66.40.017600 (300)☆117.16
16C214.66.40.021600 (300)☆111.9
16C253.75.50.025600 (480)☆68.83
16C333.75.50.033600 (480)☆63.76
16C403.45.20.04600 (560)☆58.87
16C633.250.06360051.47
16K806.88.60.08370 (140)☆254.18
16K1005.270.1450 (240)☆162.11
16K1404.96.70.14600 (270)☆122.55
16K1974.456.250.197600 (330)☆111.32
16K2204.56.30.22600 (330)☆102.89
16K3154.36.10.315600 (350)☆91.44
16K3454.26.00.345600 (370)☆85.9
16K4504.05.80.45600 (400)☆80.73
16K6304.05.80.63600 (400)☆77.26
16K8003.55.30.8600 (530)☆61.48
16K12502.84.61.2560040.83
16K20002.84.62.060038.96

Table 3 Heating Cable Specification (600V Double Conductors)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26C3.412.90.0034150783.76
26C4.412.20.0044160701.56
26C5.811.30.0058170606.16
26C8.69.900.0086180451.43
26C11.49.300.0114200400.05
26C13.89.000.0138210375.20
26C17.28.600.0172220344.90
26C238.000.023250303.25
26C34.47.500.0344280269.20
26C49.27.100.0492300243.84
26K2409.900.24180451.43
26K3209.300.32200400.05
26K3849.000.384210375.20
26K4808.600.48220344.90
26K6408.000.64250303.25
26K9607.500.96280269.20

Table 4 Heating Cable Specification (300V Double Cores)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23C3.412.00.0034200708.10
23C4.411.30.0044220629.07
23C5.810.40.0058240537.73
23C8.69.000.0086260392.56
23C11.48.400.0114280343.89
23C13.88.000.0138300314.57
23C17.27.600.0172320286.27
23C237.100.023340252.98
23C34.46.600.0344360221.19
23C49.26.200.0492380197.64
23K16010.40.16220508.37
23K2409.000.24240392.56
23K3208.400.32265343.89
23K3848.000.384280314.57
23K4807.700.48300291.91
23K6407.100.64320252.98
23K9606.500.96350216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH


Table 5 terminal specifications


Model: A, D, EModel: B
Maximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)
60015E220E115E1
60020E225E220E1
60030E340E230E2
60050E370E250E2
60070E3100E370E2

Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.

Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.


Corresponding reference table between the output power and sheath temperature


Note: when applying a copper conductor heating cable, please pay attention to the conversion of its heated hot resistance and unheated cold resistance.


China Mineral Insulated Electrical Tracing On Pipe supplier

Mineral Insulated Electrical Tracing On Pipe