Intelligent LPCB Approved Addressable Fire Alarm System Control Panel
Addressable Fire Alarm System
FP300 Addressable Fire Alarm Control Panel
The purpose of the FP300 Fire Alarm Control Panel (FACP) is to
monitor input signals, give indications and possibly activate
outputs as programmed.
It is designed to comply with EN 54-2 with qualities of simple
installation, operation and easy maintenance. The FP300 panel is an
addressable fire detection panel with 1 loop of 324 addressable
points and expansion capabilities. It is compatible with other
peripherals made by our company with its own protocol.
Fire alarm system is mostly used for laying fire system in office and commercial places. Any building needs fire alarm system, which can effectively prevent the occurrence of fire and give warning from the source.
Mains supply | 230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A |
Mains fuse | T3.15AL250V |
Operating voltage | 18.5 ~ 30V |
Recommended mains cable | Recommended mains cable Screened or standard/black mains cable, cable size 0.75mm2 |
Power rating | Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A |
Max. charging current | 1.2A |
Max. internal resistance of battery | 1.5Ω |
Battery fuse | F8AL250V |
Quiescent current (full loaded) | < 0.4A |