MIC-200-IR3 Three-band infrared flame detector
The MIC-200-IR3 three-band infrared flame detector is a reliable and high-performance flame detector. It uses advanced flame analysis and recognition technology to quickly respond to infrared radiation in a fire and has the highest false alarm immunity . The MIC-200-IR3 detector contains three narrow-band infrared sensors (4-6 microns) and optical filters, which have high sensitivity to carbon dioxide emission spectra (4.4 microns), which can effectively eliminate interference and achieve greater distances.
Features of three-band infrared flame detector:
1. Developed by the principle of three-wavelength infrared
detection, it has extremely high immunity to false alarms;
2. High-speed response to flame;
3. Built-in high-performance microprocessor;
4. Excellent anti-radio frequency and electromagnetic interference
performance;
5. Reliable system fault self-diagnosis function;
6. Two output modes of three-wire current loop and relay are
optional;
7. Patented signal processing algorithm to minimize the possibility
of false alarms;
8. Multi-level sensitivity settings to meet the different needs of
more occasions;
9. Easy to install, the detection angle can be adjusted by 360°;
10. ExdⅡ CT6 explosion-proof grade, suitable for zone 1 and zone 2
hazardous locations.
Three-band infrared flame detector parameters:
Working voltage: DC24V
Voltage range: DC18~30V
Working current: ≤30mA, alarm ≤45mA
Spectral range: 4-5um, three IR sensors
Viewing angle range: 90°
Detection distance:
Combustion Fire source size Detection distance
N-heptane 0.3m×0.3m 50m
Gas oil 0.3m×0.3m 50m
Diesel oil 0.3m×0.3m 45m
Kerosene 0.3m×0.3m 45m
Liquor essence 0.3m×0.3m 45m
Methane 0.5m×0.2m 30m
Paper 0.3m×0.3m 30m
Response time: 5-10s The response time of different media is
different
Sensitivity level: 5 levels of sensitivity (set by remote control)
Signal output: 4~20mA three-wire system output
Fault ≤3mA, normal 5mA, alarm 15mA
Relay type 2 relays (fire alarm, fault) normally open contact
output, contact capacity 30V, 3A
Working temperature: -40℃~70℃
Working humidity: ≤95%RH (no condensation)
Electromagnetic compatibility and environmental test: Meet the
requirements of the national GB16838 standard, applicable to high
temperature, high salt, high temperature and low temperature
environments. Anti-point transient, surge voltage interference,
anti-static interference
Explosion-proof certification: ExdⅡCT6/DIP A20 TA, T6
Degree of protection: IP 66
Shell material: aluminum alloy, surface anti-corrosion paint
sprayed plastic
Electrical interface: M20X1.5mm
Meet the standards: GB15631-2008, GB3836-2000 series
Weight: 1.7kg
• Offshore platforms & vessels (FPSO’s)
• Downstream chemical processing plants
• Gas transport and pipelines
• Large storage areas & buildings