SHSL-D4 Series Heat Exchanger Radiator For Power Station
Features
Air discharge direction | |
Performance ranges | Cooling capacity: from 5 to 649 kw |
High efficiency heat exchanger | Capacity designs for maximizing the heat transfer relative to the
energy consumption of the fan. |
Fan | Only choose low specific energy consumption fans. |
Testing | Heat exchangers are supplied clean and tested at a pressure of 30 bars |
Options | Coil design refrigerant: water, oil, glycol. |
Technical parameter
Dry cooler D4 series parameter(fin space 2.1mm)
Type | D4-428- 10X800 | D4-488- 10X800 | D4-510- 10X800 | D4-520- 12X800 | D4-591- 12X800 | D4-617- 12X800 | D4-724- 14X800 | D4-792- 16X800 | |||||||
Capacity | Water | 35℃ outdoor temp. | Inlet | 45℃, | KW | 427.6 | 488.1 | 509.9 | 519.9 | 590.7 | 616.7 | 723.6 | 791.6 | ||
outlet | 40℃ | ||||||||||||||
20% Glycol | Inlet | 45℃ | 411 | 476.6 | 498.6 | 503.5 | 579.2 | 605.5 | 712.4 | 777.2 | |||||
outlet | 40℃ | ||||||||||||||
Medium | Water flow | M3/h | 74.3 | 84.9 | 88.7 | 90.4 | 102.7 | 107.2 | 125.8 | 137.6 | |||||
Pressure drop | kPa | 28 | 60 | 48 | 43 | 99 | 78 | 99 | 99 | ||||||
Air flow | M3/h | 216938 | 202183 | 193538 | 260320 | 242613 | 232238 | 270940 | 323168 | ||||||
Fan motor(400V/3N/50HZ) | W | 18000 | 18000 | 18000 | 21600 | 21600 | 21600 | 25200 | 28800 | ||||||
A | 38 | 38 | 38 | 45.6 | 45.6 | 45.6 | 53.2 | 60.8 | |||||||
Fan | No X φ | 2X5X800 | 2X5X800 | 2X5X800 | 2X6X800 | 2X6X800 | 2X6X800 | 2X7X800 | 2X8X800 | ||||||
Sound pressure level | dB(A) | 60 | 60 | 60 | 62 | 62 | 62 | 64 | 66 | ||||||
10m | |||||||||||||||
Dimension | L | mm | 6270 | 6270 | 6270 | 7470 | 7470 | 7470 | 8670 | 9870 | |||||
W | mm | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | ||||||
H | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | ||||||
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | ||||||
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | ||||||
Product weight(empty) | kg | 2159 | 2250 | 2327 | 2480 | 2568 | 2741 | 2947 | 3342 |
Application of radiator in cooling diesel generator set:
Cooling method: The water in the dry cooler system uses a heat
exchanger to cool the circulating water or oil inside the
generator.
Reference:
For power plant | Country: Hongkong | Country: Russia | |