Package Type Hygienic Air Handling Units Clean Room HVAC Equipment


According to the clean operating room design specifications, the clean air conditioning system must have core technical indicators such as constant temperature, constant humidity, fresh air treatment, air purification, and ensuring the positive and negative pressure difference in the controlled area to achieve the design requirements for controlling the concentration of bacteria and reducing the risk of infection. Clean air conditioners have multiple functions such as air purification, transportation, cooling, dehumidification, humidification, heating, heat recovery, and intelligent control, providing users with clean environment system solutions suitable for different purification levels and different working conditions.

AHU model representation method:


Unit quick selection table (air volume)

ModelNominal air volume m³/hWindward area of coil㎡Wind speed of the coil(m/s)
2.002.252.502.753.003.25
m³/h
SLZK015W15000.16115212961440158417281872
SLZK018W18000.2144016201800198021602340
SLZK022W22000.24172819442160237625922808
SLZK032W32000.35252028353150346537804095
SLZK038W38000.42302434023780415845364914
SLZK050W50000.56403245365040554460486552
SLZK063W63000.7504056706300693075608190
SLZK072W72000.8576064807200792086409360
SLZK095W95001.04748884249360102961123212168
SLZK120W120001.393601053011700128701404015210
SLZK150W150001.69121681368915210167311825219773
SLZK180W180002.08149761684818720205922246424336
SLZK230W230002.56184322073623040253442764829952
SLZK270W270003.04218882462427360300963283235568
SLZK320W320003.61259922924132490357393898842237
SLZK370W370004.18300963385837620413824514448906
SLZK430W430004.75342003847542750470255130055575
SLZK500W500005.5396004455049500544505940064350
SLZK550W550006.16443524989655440609846652872072
SLZK630W630007504005670063000693007560081900
SLZK700W700007.84564486350470560776168467291728
SLZK760W760008.5612006885076500841509180099450
SLZK850W850009.5268544771128568094248102816111384
SLZK930W9300010.36745928391693240102564111888121212
SLZK1000W10000011.478258492907103230113553123876134199
SLZK1100W11000012.5890576101898113220124542135864147186

Note: 1. It is recommended to add a water baffle if the wind speed exceeds 2.75m/s.


Unit quick selection table (cooling capacity of coil section under return air condition)

ModelNominal air volume m³/h4 rows6 rows8 rows
Cooling capacityWater volumeCooling capacityWater volumeCooling capacityWater volume
kWm³/hkWm³/hkWm³/h
SLZK015W15008.21.410.91.8713.22.27
SLZK018W180010.21.813.62.3416.52.84
SLZK022W220012.62.216.42.8219.83.41
SLZK032W320017.83.123.84.0928.84.95
SLZK038W380021.53.728.64.9234.65.95
SLZK050W500028.74.938.16.5546.27.95
SLZK063W630035.86.247.88.2257.59.89
SLZK072W720041.17.154.69.3966.111.37
SLZK095W950053.39.270.812.1885.614.72
SLZK120W1200066.711.588.615.24107.118.42
SLZK150W1500086.614.9115.319.83138.623.84
SLZK180W18000106.518.3141.824.39170.329.29
SLZK230W23000131.222.6172.929.74210.536.21
SLZK270W27000155.826.8206.835.57248.642.76
SLZK320W32000185.131.8245.242.17296.551.00
SLZK370W37000214.236.8285.149.04341.858.79
SLZK430W43000243.341.8323.655.66385.666.32
SLZK500W50000281.548.4374.564.41450.377.45
SLZK550W55000315.754.3419.372.12500.486.07
SLZK630W63000358.661.7476.581.96560.496.39
SLZK700W70000400.568.9534.191.87640.5110.17
SLZK760W76000432.674.4578.299.45690.5118.77
SLZK850W85000482.583.0645.8111.08765.8131.72
SLZK930W93000520.689.5702.3120.80830.5142.85
SLZK1000W100000576.199.1778.4133.88940.8161.82
SLZK1100W110000630.6108.5850.6146.30970.5166.93

Note:

1. The inlet temperature of chilled water is 7°C, and the outlet temperature is 12°C;

2. Return air condition: inlet air dry bulb temperature 27℃, wet bulb temperature 19.5℃;

3. The above parameters are for reference only. If the working conditions and coil circuit arrangement are changed, the parameters will change.


Unit quick selection table(cooling capacity of coil section under fresh air condition)

ModelNominal air volume m³/h4 rows6 rows8 rows
Cooling capacityWater volumeCooling capacityWater volumeCooling capacityWater volume
kWm³/hkWm³/hkWm³/h
SLZK015W150018.93.323.54.0428.14.83
SLZK018W180023.54.029.45.0635.16.04
SLZK022W220028.34.935.36.0742.27.25
SLZK032W320041.37.151.48.8461.510.57
SLZK038W380049.58.561.710.6173.812.69
SLZK050W500066.211.482.314.1598.416.92
SLZK063W630082.314.2102.817.68122.921.15
SLZK072W720094.516.3117.520.21140.524.17
SLZK095W9500122.921.1152.826.27182.731.42
SLZK120W12000153.226.4190.932.84228.339.27
SLZK150W15000195.633.6248.242.69296.851.05
SLZK180W18000245.642.2305.552.55365.362.83
SLZK230W23000302.152.0376.064.67449.677.33
SLZK270W27000358.761.7446.576.80533.991.83
SLZK320W32000426.173.3530.291.20634.0109.05
SLZK370W37000492.884.8613.9105.60734.1126.27
SLZK430W43000560.896.5697.7120.00834.2143.49
SLZK500W50000648.9111.6807.8138.94965.9166.14
SLZK550W55000727.6125.1904.8155.621081.9186.08
SLZK630W63000826.4142.11028.1176.841229.4211.45
SLZK700W70000924.8159.11151.5198.061376.9236.83
SLZK760W760001005.4172.91248.4214.731492.8256.76
SLZK850W850001124.3193.41398.3240.501672.0287.58
SLZK930W930001200.6206.51514.6260.511812.4311.73
SLZK1000W1000001320.6227.11671.4287.482010.3345.77
SLZK1100W1100001450.7249.51825.7314.022186.5376.08

Note:

1. The inlet temperature of chilled water is 7℃, and the outlet temperature is 12℃;

2. Fresh air conditions: inlet air dry bulb temperature 35℃, wet bulb temperature 28℃;

3. The above parameters are for reference only. If the working conditions and coil circuit arrangement are changed, the parameters will change.


Unit quick selection table(hot water coil heating capacity)

ModelNominal air volume m³/hReturn air conditionFresh air condition
2 rows3 rows4 rows2 rows3 rows4 rows
heating capacityheating capacityheating capacityheating capacityheating capacityheating capacity
kWkWkWkWkWkW
SLZK015W15009.412.514.811.115.118.1
SLZK018W180011.815.618.513.918.922.6
SLZK022W220014.118.822.216.722.727.2
SLZK032W320020.627.332.424.333.039.6
SLZK038W380024.732.838.929.139.647.5
SLZK050W500032.943.851.838.952.963.4
SLZK063W630041.154.764.848.666.179.2
SLZK072W720047.062.574.055.575.590.5
SLZK095W950061.181.396.272.298.2117.7
SLZK120W1200076.4101.6120.390.2122.7147.1
SLZK150W1500099.3132.0156.3117.2159.5191.2
SLZK180W18000122.2162.5192.4144.3196.3235.3
SLZK230W23000150.4200.0236.8177.6241.6289.6
SLZK270W27000178.6237.5281.2210.9286.9343.9
SLZK320W32000212.1282.0333.9250.4340.7408.4
SLZK370W37000245.6326.6386.7290.0394.5472.9
SLZK430W43000279.1371.1439.4329.5448.3537.3
SLZK500W50000323.1429.7508.8381.6519.1622.2
SLZK550W55000361.9481.3569.8427.4581.4696.9
SLZK630W63000411.3546.9647.5485.6660.6791.9
SLZK700W70000460.6612.5725.2543.9739.9886.9
SLZK760W76000499.4664.1786.3589.7802.2961.6
SLZK850W85000559.3743.8880.6660.5898.51077.0
SLZK930W93000608.7809.4958.3718.7977.71172.0
SLZK1000W100000673.9896.11061.0795.71082.51297.5
SLZK1100W110000739.1982.81163.7872.71187.21423.1

Note:

1. The inlet temperature of hot water is 60°C, and the outlet temperature is 50°C;

2. Return air condition: inlet air dry bulb temperature 15℃; fresh air condition: inlet air dry bulb temperature 7℃;

3. The above parameters are for reference only. If the working conditions and coil circuit arrangement are changed, the parameters will change.

China Package Type Hygienic Air Handling Units Clean Room HVAC Equipment supplier