Rabbit Moose Aluminium Conductor Steel Reinforced For Power Transmission
Aluminium Conductor Steel Reinforced Application:
1. The long-time working temperature of cable should not be higher
than 250℃.
2. While installation the ambient temperature should not be lower
than -20℃.
3. When core is in short circus (max 5s) the temperature should not
exceed 250℃ Specifications
Aluminium Conductor Steel Reinforced Parameters
Code | Size (AWG/MCM) | Number of Strands(mm) | Weight(kg/km) | Rated Strength(kg) |
Rose | 4 | 7*1.96 | 58.3 | 399 |
Iris | 2 | 7*2.47 | 92.7 | 611 |
Pansy | 1 | 7*2.78 | 117 | 740 |
Poppy | 1/0 | 7*3.12 | 147.5 | 897 |
Aster | 2/0 | 7*3.5 | 186 | 1375 |
Used bare overhead transmission cable and as primary and secondary distribution cable acsr offers optimal strength for line design without sacrificing ampacity.
ACSR Conductor
ACSR is a composite concentric-lay-stranded conductor. Galvanized steel strand or strands form the central core of the conductor,around which is stranded one or more layers of EC Grade Aluminum wires. The steel core may consist of a single strand or a concentricstranded cable of 7, 19, 37, or more wires. Numerous combinations of aluminum and steel strands and layers are possible. If you haveany suggestions or opinions about our products,please leave a message,and we will immediately answer your questions. Thanks for your support.
Service Performance:
(1). The permissible long-time operating temperature for aerial
conductor is 70℃.
(2). Under the circumstance that rare climate is occurring and ice
coverage rate low in heavy ice area, the biggest stress of cable at
the lowest point of the sag should not exceed 60% of the short-time
destructive power.
(3). When connecting conductors, the conductor beside the
connecting tube cant be prominent. Otherwise, the force on the
operating conductors will be unbalanced. After connectors are
install, the connecting tube should be painted by moisture-proof
varnish in order to protect it from corrosion.
(4). Under installation, the arc downing stress of all the
conductors should be the same. With in the permissible distance of
crossing buildings or dropping to the ground, the stress can be
10-15% higher than regular stress.