Electro Pneumatic Single Seat Valves LCD Control Valve Positioner

Brand Name:POWERFLOW
Certification:ISO9001. CE. Nepsi
Model Number:1600
Minimum Order Quantity:1 Nos
Delivery Time:10-15 Days
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Hangzhou Zhejiang China
Address: Unit E, NO.11 XiYuan Eight Road, XiHu District, HangZhou City, Zhejiang Province, China.
Supplier`s last login times: within 46 hours
Product Details Company Profile
Product Details

1600 Series Autotune Smart Electro-pneumatic Valve Positioner for Single Seat Valves


1. Product Description


1600 series intelligent electro-pneumatic valve positioner is simple to operate and has plenty software functions. It can easily be operated via the LCD and keypad.

The product is designed for integral pneumatic control valve, particularly suitable for diaphragm valves and angle seat valves.

The positioner adjusts the valve position quickly and accurately via detecting the position sensor signal, .


​2.Technical Datas


MaterialPC,PA6-GF30,Stainless Steel,SI
Power supply24V DC ±10%
Set-point signal0/4-20mA or 0-5/10 V
Input resistance for set-point signal240Ω at 0/4-20mA, 21KΩ at 0-5/10V

Control medium

Dust concentration

Particle density

Pressure condensation point

Oil concentration

Neutral gases, air DIN ISO 8573-1

Class 5 (<40μm particle size)

Class 5 (<10mg/m3)

Cass 3 (<-20°C)

Class 5 (<25mg/m3)

Ambient Temperature0-70°C
Pneumatic ConnectionPlug-in hose connector G1/4(internal Φ6mm)
Electrical Connection

M12 3-pins B-coded(cable ø 4-6mm)

M12 4-pins D-coded(cable ø 4-6mm)

M12 5-pins A-coded(cable ø 4-6mm)

Supply Pressure3~7 bar, specific values depending on the actuator
Air Flow Rate17 L/min, 58 L/min(only single-acting)
Stroke Control Range

Linear 5-50mm

Rotary 90°

InstallationAs required, Preferably with actuator in upright position, Screw.
Protection ClassIP65
Power Consumption<5W
Explosion ProofEx nA IIC T4

3. Product type selection



4. Dimensions



5. Additional software functions


  • Setting safety position for the position controller
  • Configuration of signal level fault detection
  • The binary outputs activating
  • Configuration of the outputs
  • The control parameters calibrating
  • Manual control rate setting
  • Code protection
  • Selection of the transfer characteristic between set-point value and stroke
  • Sealing function for position controller
  • Effective sense of direction between input signal and set-point value
  • Limit of the machanical stroke range
  • Control parameters setting

6. Signal flow diagram