Add to Cart
ISO 9239-1: Flooring fire reaction test - Part 1: Combustion
performance of flooring materials tested by radiant heat
ASTM E 648: Critical Radiant Flux of Floor standard test - covering
system uses radiant heat energy
ASTM E 970: Using a Radiant Heat Energy Source, test insulation
floorinsulationinsulation standard test for Critical Radiant Flux
using a radiant heat energy.
NFPA 253: Standard Test Method for using radiant heat energy, test
plates overlay system Critical Radiant Flux
1, All structural components of flooring radiant panel apparatus
are made of stainless steel, nice appearance, corrosion resistance;
2, The radiation source is a porous ceramic heat radiating plate
300mmX450mm, tilted 30 °;
3, Imported calorimeter from US Medtherm company, range 50KW /m;
4, Igniters diameter of 0.7mm from the bottom of the center line of
each 60-degree position according to standard request.
5, The standard plate is made of thick 20 ± 1mm, density 850 ±
100kg / m³ without coating made of calcium silicate board; size
1050X250mm
6, Small stainless steel auxiliary ignition burner ignited sample.
7, Imported flow control meter from Japan, precise control of the
flow of propane
8, This flooring radiant panel apparatus is equipped with air
blower providing air, mixed gas through the venturi mixing test
gas,
9, The specimen holder is made of stainless steel and an overall
dimension of 1140mm x 320 mm.
1, The optical system comprising a light source color temperature
is 2900 ± 100 K incandescent,lightreceiving silicon photodiode with
an optical path test shutter, 0% and 100%, to facilitate the use of
calibration;
2, Imported light battery module measuring light attenuation. The
system automatically calculates and generates a light transmittance
curve translucent; printable Scribble
3, One button automatic and five level calibration system by
computer.
1, Heat radiation pyrometer accuracy of ± 0.5 ºC, away from the
radiation board about 1.4m;
2, Radiation pyrometer sensitivity constant in the wavelength range
1um ~ 9um;
3, High-performa
1 | Electrical | AC220V±10%, 50Hz;5KW |
2 | Ambient Temperature | Operating 10°C to 35°C |
3 | Dimensions | Control box: 600(W)×750(D)×1600(H)mm Test part:Length1.4× width1.0× High2.2 M³ |
4 | Gas Supplies | Propane and air compressor |
5 | Weight | 350KG |