Transformer No Load Loss and Load Loss Measurement Equipment

Brand Name:AI
Certification:ISO9001
Model Number:KFZ
Minimum Order Quantity:1 set Transformer No Load and Load Measurement Equipment
Delivery Time:15 days
Payment Terms:Western Union, T/T, L/C
Contact Now

Add to Cart

Verified Supplier
Location: Changsha Hunan China
Address: Hi-tech Developing Industrial Area, Liuyang City,Changsha,Hunan Province,China
Supplier`s last login times: within 30 hours
Product Details Company Profile
Product Details

Introduction:

Transformer No Load and Load Measurement Equipment is designed for transformer capacity, load loss and no load loss testing, it can measure following parameters of transformer: capacity, transformer type, no-load current, no-load loss, short circuit (load) loss and impedance voltage.

Transformer No Load and Load Measurement Equipment is reliable, accurate, simple for wiring and operation.


Features:

  • Measurement range of voltage, current and capacity is wide, and measurement range can convert automatically. For example, the instrument can complete load test under full current of distribution transformer below 1000kVA. The load test of distribution transformers below 3150kV can be completed under 1/3 of the rated current (under 1/3 rated current, the instrument can be converted to the load loss parameter under the rated current).

  • When testing load and no load loss of three phase transformer, it can automatically determine whether the wiring is correct or not, and display vector of three phase voltage and current.

  • All test results can be automatically corrected by the Transformer No Load and Load Measurement Equipment.

  • LCD 20 * 240 large screen.

  • Users can preset 40 sets sample parameters, and these parameters can be deleted or added at any time.

  • With real-time electronic clock, which can automatically record test date and time.

  • 500 sets test data can be stored in the tester, meanwhile, users can connect the tester with computer to upload the data.

  • Transformer No Load and Load Measurement Equipment adopts built-in printer, users can print test result immediately after test.

  • Allows external current transformers or voltage transformers to extend measurement range, so it can test any kinds of transformers.


Specifications:


1Test Parameters

Transformer capacity, no-load current, no-load loss,

short circuit voltage, short circuit (load) loss

2Working powerInput voltage185Vac~250Vac
Allowable input voltage85Vac~264Vac
Frequency50/60Hz
Allowable frequency45Hz~65Hz
Input power40VA
3AC voltageRange10~650V
Resolution0.001V
Accuracy0.2%±0.001V
4AC CurrentRange0.5~60A
Resolution0.001A
Accuracy0.2%±0.001A
5FrequencyRange45Hz~65Hz
Resolution0.001Hz
Accuracy0.2%±0.001Hz
6PowerRange0~39kW
Resolution0.001kW
Accuracy

<±0.5%(CosΦ>0.1) ±1.0%(0.02<CosΦ<0.1)

7Capacity test range10kV Dry type transformer30kVA~3150kVA
10kV Oil immersed transformer30kVA~3150kVA
35kV Oil immersed transformer50kVA~31500kVA
20kV Dry type transformer50kVA~2500kVA
35kV Dry type transformer50kVA~2000kVA
8EnvironmentOperating temperature-10℃~+50℃
Storage temperature-25℃~+70℃
Relative humidity5%~95%
9Dimension40cm*30cm*22cm
10Weight8kg (Excluding accessories)

China Transformer No Load Loss and Load Loss Measurement Equipment supplier

Transformer No Load Loss and Load Loss Measurement Equipment

Inquiry Cart 0