Operation of vacuum circuit breaker
The main aim of any circuit breaker is to quench arc during current
zero crossing, by establishing high dielectric strength in between
the contacts so that reestablishment of arc after current zero
becomes impossible. The dielectric strength of vacuum is eight
times greater than that of air and four times greater than that of
SF6 gas. This high dielectric strength makes it possible to quench
a vacuum arc within very small contact gap. For short contact gap,
low
contact mass and no compression of medium the drive energy required
in vacuum circuit breaker is minimum. When two face to face contact
areas are just being separated to each other, they are not done so
instantly. Instead, as the contact area on the contact face is
being reduced and ultimately comes to a point and then they are
finally de-touched. This happens in a fraction of micro second. At
this instant of de-touching of contacts in a vacuum, the current
through the contacts concentrated on that last contact point on the
contact surface and makes a hot spot there. As the medium is
vacuum, the metal on the contact surface gets easily vaporized due
to that hot spot and create a conducting media for arc path.
Therefore, the material constituting the arc is very small and thus
a feeble arc is established even with high current interruption.
The arc will be initiated and continues until the onset of next
current zero. Th figure below shows the cross section assembly of a
VCB.
Item | Unit | Data | |||
Rated insulation level | 1min power frequency withstand voltage | Dry | KV | 42 | 65 |
Wet | 34 | 50 | |||
Lightning impulse withstand voltage | 75 | 1250 | |||
Rated short circuit breaking current | KA | 20;16;12.5 | 20;16;12.5 | ||
Rated short circuit breaking times | Times | 30 | 30 | ||
Rated short-circuit switching current | KA | 50 | 50 | ||
Rated peak withstand current | |||||
Rated short-circuit withstand current | 20 | 20 | |||
Rated short circuit duration | S | 4 | 4 | ||
Opening time(SHT) | Maximum operating voltage | ms | 15-50 | 15-50 | |
Rated operating voltage | |||||
Minimum operating voltage | 30-60 | 30-60 | |||
Closing time | ms | 25-50 | 25-50 | ||
Full-off time | ≤100 | ≤100 | |||
Arcing time | 20 | 20 | |||
Mechanical life | Times | 1000 | 1000 | ||
Charging motor rated input power | W | 40 | 40 | ||
Rated operating voltage and auxiliary voltage circuit | V | DC220,110,24 | DC220,110,24 | ||
AC220,110,24 | AC220,110,24 | ||||
Rated voltage of the storage time | S | ≤10 | ≤10 | ||
Over current release | Rated current | A | 5 | 5 | |
Trip current accuracy | % | ±10 | ±10 |
Q1. Can we have our logo or company name to be printed on your
products or the package?
Yes,you can.Logo and company name can be printed on our products by
silk screen printing.You can send us the artwork by email in JPEG
or TIFF format.
Q2. What is lead time?
Usually 3-15 working days, On-Time delivery
Q3. Why us?
All products comply with the requirements of GB national standards,
IC, ANSI and other international standards, and the requirements of
company's technology standards.
Q4. How do you make our business long-term and good relationship?
1. Our high quality and competitive price are the most important
factors to maintain long-term and good relation -ship with our
customers.
2. Good service is our basic principle for every customers.
Q5. Can I have a visit to your factory before the order?
Sure,welcome to visit our factory.