50Hz Global Warranty Super Silent 200kva Cummins Diesel Generator with Stamford Alternator
Product Description
1. SPECIFICATIONS OF GEN-SET
1.1Set ModelBS-C200
1.2Prime at 50HZ, 40℃ ambient150KW 188KVA
1.3Standby at 50HZ, 40℃ ambient165KW 200KVA
1.4Rated Gen-set output230/400V 50Hz
1.5Rated Relative humidity≤ 60 %
1.6Dimension (L×W×H)2510X960X1600mm
1.7Weight1800kg
1.8Fuel consumption 100% prime load45L/h
1.9Total heat radiated to ambient17KW
1.11Structure of Gen-setThe Gen-set adopt integrative structure, engine is fix on high strength steel basic frame, anti vibration instrument between the engine and basic frame, cooling fan have protecting cap, control cabinet and circuit breaker installed on Gen-set.
1.12Control system (Optional)Basic control panel or Advanced control panel with automatically start-up function and other function.
2. SPECIFICATIONS OF ENGINE
2.1Engine BrandDCEC Cummins
2.2Engine Model6CTA8.3-G2
2.3Governor/ClassElectrical
2.4Cylinder NO.6
2.5Engine buildLine
2.6Fuel spray patternPT direct injection
2.7start-up method24V, electric
2.8AspirationTurbocharged
2.9Cooling modeRadiator cooled (enclose water)
2.10Bore and stroke114×135 mm
2.11Compression ratio17.3:1
2.12Displacement8.3 L
2.13Engine Prime Power at 1500rpm183KWm
2.14Engine Standby Power at 1500rpm203KWm
2.15Battery capacity100A/hr
2.16Starting/Min temperature4℃
2.17Lubrication oil capacity16L
2.18Coolant capacity - radiator and engine (40℃)28L
2.19Exhaust temp - full load prime498℃
2.20Exhaust gas flow - full load prime1020m 3/h
2.21Exhaust gas back pressure max76mmHg
2.22Air flow - radiator (40℃ ambient)2.1 m 3/s
2.23Pusher fan head (duct allowance) 40℃10mmH 2O
2.24Air intake - engine- full load prime248m 3/h
2.25Standard Air intake temp25℃
2.26Fuel type#0 Diesel (Natural temperature)
2.27Filter systemAdopt whole changeable lubricating oil, fuel filter and air filter
2.28Exhaust systemAdopt industrial high efficiency muffler and ripple pipe
3. SPECIFICATIONS OF ALTENATOR
3.1Alternator ModelStamford/UCI274H
3.2Alternator TypeA.C. Synchronous
3.3Rated Voltage230/400V
3.4Rated Frequency50HZ
3.5Rated speed1500 RPM
3.6Voltage regulation modeAuto
3.7Alternator voltage regulation±0.5%
3.8Exciting modeBrushless self exciting
3.9Power factor0.8 (lagging)
3.10Phase & wires3 phase 12 wires
3.11Rated currency144.3A
3.12Efficiency0.903
3.13Insulation classH
3.14Protection classIP23



FAQ

Q : Do you offer OEM service?
A : Yes

Q : What is the difference between Prime power and Standby power?
A : Prime power is 12hours continous power,one hour 10% over load in every 12 running hours is allowed .
Standby power is the limit value of maximum output for emergency use . Overloading is prohibited
Q : What about the warranty
A : Guarantee for one year or 1000 hours (accord to whichever reach first) from ex-factory date .During the

guarantee period ,our company will provide the free easy damaged spare part for problems caused by our

quality of production or raw material except the damageable spare parts of diesel engine caused by