Mineral Insulated Cable used in Building, industrial, airport,
power station, power supply and others
Method of choosing
1. In the following cases, flexible mineral insulated cables with
plastic sheaths should be used:
The cable is placed in an environment that corrodes the copper
sheath.
The cables are buried directly or laid through pipes.
The cables are laid in non-technical spaces of buildings and have
aesthetic requirements. Where there is a fire protection
requirement, a halogen-free and low-smoke plastic enclosure should
be used.
Nominal Cross section | Outer Diameter approx. | Weight of cable approx. | Voltage drop | Mini bending radius |
Single phase | Three phase |
mm2 | mm | kg/km | V/A.km | V/A.km | mm |
3 x 1.5 | 10.7 | 273.3 | 30.8 | 26.7 | 160.5 |
3 x 2.5 | 11.6 | 319.4 | 18.9 | 16.4 | 174.0 |
3 x 4 | 12.5 | 398.3 | 11.8 | 10.2 | 187.5 |
3 x 6 | 13.7 | 479.9 | 7.9 | 6.81 | 205.5 |
3 x 10 | 17.3 | 636.1 | 4.7 | 4.05 | 259.5 |
3 x 16 | 19.5 | 846.8 | 2.94 | 2.55 | 292.5 |
3 x 25 | 22.3 | 1,192.9 | 1.87 | 1.62 | 334.5 |
3 x 35 | 25.2 | 1,518.8 | 1.35 | 1.17 | 378.0 |
3 x 50 | 28.6 | 1,950.5 | 1.01 | 0.87 | 429.0 |
3 x 70 | 32.7 | 2,629.9 | 0.71 | 0.61 | 490.5 |
3 x 95 | 37.1 | 3,588.8 | 0.52 | 0.454 | 556.5 |
3 x 120 | 40.9 | 4,379.3 | 0.43 | 0.371 | 613.5 |
2. Specification selection
Determine the maximum operating temperature of the cable according
to the cable laying environment, reasonably select the
corresponding cable current, and determine the cable
specifications.
2.1: There are two types of flexible mineral insulated cables
according to the cable temperature
Carrying capacity: at 70°C
Ampacity at 105°C
2.2: The current carrying capacity of the selected cable should be
in accordance with the normal operating temperature of 70 0 C under
the following laying conditions:
Clean lines along walls, brackets, roofs and bridges.
It is routed together with other types of cables in the same
bridge, shaft, cable trench, and cable tunnel.
Other places where the temperature of the cable sheath is too high
may cause personal injury or equipment damage.
2.3: Place the cables in the bridge, cable trench and the place
where the unmanned machine wears the pipe. The current carrying
capacity can be selected according to the normal operating
temperature 105 0 C
. 2.4: The specifications of flexible mineral insulated cables
should be reasonably determined according to the actual length of
the line and the length of delivery of the cable.