3 phase step down 6kv 10kv 11kv 22kv 35kv voltage distribution oil immersed transformer China transformer manufacturers
Our transformer is equipped characters as low loss, low noise,
strong protection for thunder and lighting, well anti-shortcut
capacity and fine appearance etc. It combines advanced equipments
and manufacturing process, and it has four remote functions: remote
communication, remote test, remote adjustment and remote control.
By remote control from a computer, the power station could be work
without any works on watch on the night. All our transformer has
passed the test by National Mechanical & Industrial Bureau and
National Power Company. The transformer is mainly used in power
network, and the projects of power distribution.
Core equipped with advanced three steps: vertical and horizontal
and horizontal cut, lap and multi-stage. It disperses the air
distribution, improve the magnetic path. Decrease the no load loss,
no load current and noise. energy-saving power transformer
Core adopts series measures dragged panel, pressed the coil,
particular glue for silicon steel to increase the strength of
mechanism. energy-saving power transformer
New structure of high and low voltage winding, reasonable
arrangement for oil tube and connection which increasing the
capacity of mechanical strength and anti-shortcut.
The tank is bell type or core suspension type, the wall of tank is
as wave form.
Structural features
The core is made of high-quality cold-rolled grain oriented silicon steel sheet in a full inclined pore-free structure. Low magnetic steel plate is used for pulling plate, which firmly connects the upper and lower clamps with the core to form a steel structure.This structure generates less no-load loss and lower noise. The burr of silicon steel sheet shear port shall not be greater than 0.02mm. The no-load performance index is superior to the national standard of China.
According to the capacity of the transformer, the winding is made
of cylinder, spiral, continuous and other structures. For the 110kV
UHV transformer, the winding adopts tangled or inner screen
structureso as to effectively improve the distribution of impulse
voltage. The conductor uses transposed conductor or composite
conductor to reduce the additional loss of the winding. Uses of
computer simulation to calculate the impact characteristics of
electric field and windingensures excellent electrical
characteristics and impact strength of the winding. Effective
measures are adopted in the process to ensure its safe and reliable
operation.
The pressing structure of 110kV UHV Transformer body uses round
insulating pressing plate. Adoption of theintegrated winding
assemblyimproves the reliability of the product.
The oil tank is a flat top bell-type structure with
folded-plate-type reinforcing iron welded on the tank wall,which
improves the mechanical strength of the oil tank. In order to
reduce the stray loss of the transformer, the inner wall of a large
transformer is equipped with magnetic shield.
In order to prevent the displacement of 110kV UHV Transformerbody
during transportation, a positioning device is set in the oil tank.
A sealed oil conservator is used to isolate the transformer oil
from the air to avoid moisture and oil aging. The end of oil
conservatoris equipped with a pointer-type oil level gauge.
According to the weight of the transformer oil, a pressure relief
valve is installed on the top of the oil tank to ensure the safe
operation of the product.
Cooling method is normally air-cooled or nature cooled (ONAF /
ONAN) . The transformer operates 100% full load when ONAF and 80%
of the full load when ONAN.
Heat dissipation uses sheet radiator, which generates compact
shape. The sheet to sheet welding of the radiator is one-time
forming, which is reliable. Adopted high-speed low-noise
fangenerally blow in horizontal direction.
The start and stop of the fan is controlled by oil temperature and
load. A control cabinet is attached for the transformer fan.
The oil conservator is ofa capsuleshape, which equipped with oil
resistant, temperature resistant and air tight sealed capsules to
isolate the oil from the outside air. The outside of the capsule is
oil, and the inside is air. In order to further improve the
reliability of the transformer, a silica gel moisture-absorber is
used to exchange air in the air chamber of the capsule with the
outside air .
Note: Due to continuous product improvement, the dimensions provided in this sample are for reference only. If necessary, our company can design and produce according to user requirements. Please contact the company in time.
Main technical parameters | ||
Main circuit rated voltage(V) | .......................... | Ac 400 (600) |
Rated voltage of auxiliary circuit (V) | .......................... | Ac 220/380 (400) dc 110/220 |
Rated frequency (Hz) | .......................... | 50(60) |
Rated insulation voltage(V) | .......................... | 690(1000) |
Rated current(A) | The level of bus | ≤6000 |
Rated short-time bus withstand current (kA/1s) | .......................... | 50,80 |
Rated peak withstand current of bus (kA/0.1s) | .......................... | 105,176 |
Power frequency test voltage (V/1min) | main circuit | 2500 |
Auxiliary circuit | 1760 | |
bus | Three-phase four-wire system | A,B,C,PEN |
Three-phase five-wire system | A,B,C,PE,N | |
Protection grade | .......................... | IP30 |
·Order instructions:
1. The customer needs provide main parameters of the transformer (input and output voltage, capacity, loss, etc.)
2. Other customer requirements