Electrical Safety AC DC High Voltage And Insulation Resistance Tester

Brand Name:Sinuo
Certification:Calibration Certificate (Cost Additional)
Model Number:SN9636H
Minimum Order Quantity:1
Delivery Time:20 Days
Payment Terms:L/C, T/T, Western Union, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Location: Guangzhou Guangdong China
Address: Room 101, 1st Floor, No. 6, Third Street, Pingshan Industrial Zone 511495, Shibi Street, Panyu District, Guangzhou, China
Supplier`s last login times: within 36 hours
Product Details Company Profile
Product Details

AC/DC High Voltage Withstand & Insulation Resistance Testing Equipment


Product information:


■Meet the test requirements of general electrical safety standards such as IEC60335.1, UL60335.1, GB4706.1, etc.
■ Up to 100 groups of test condition memory, model of each group can be set, easy to find, test data can be saved via USB(optional)
■ Voltage ramp-up and ramp-down functions to meet the requirements of new industry standards;
■ Breakdown current upper and lower limit preset, intelligent judgment;
■ Digital closed-loop feedback control mode, automatic voltage regulation mode, automatic correction of output voltage/current, and not affected by the external power grid, ensuring the accuracy of the test

■ High-definition LCD display and simple panel operation


Technical Parameters:


ModelSN9636H
Test ContentsAC and DC withstand voltage, insulation resistance
Data storage methodUSB (optional)
External interfaceAlarm LAMP, PLC, RS-232
AC withstand voltage
Output voltage setting range / accuracy

AC 200~5000V

±(1.5%×setting+5digits)

Breakdown current measurement range / accuracy

0.10~100.0mA

±(1.5%×setting+5digits)

Breakdown current preset alarm range

Upper limit :0.1~100.0mA;

Lower limit :0.00~5.00mA

Test time range / resolution1~300s 1s/step
DC withstand voltage
Output voltage setting range / accuracyDC 200~5000V ±(1.5%× setting +5 digits )
Breakdown current measurement range / accuracy0.10~10.00mA ±(1.5%×display+5 digits)
Breakdown current preset alarm rangeUpper limit: 0.10~10.00mA; lower limit: 0.00~5.00mA
Test time range / resolution1~300s 1s/step
Insulation resistance
Output voltage setting range / accuracyDC500/1000V ±(1.5%× reading +5 digits )
Insulation resistance measurement range / accuracy

1~2000MΩ:

≤100MΩ:± (5%×display+3 digits )

>100 MΩ:± (8%× display +8 digits)

Insulation resistance alarm setting range

Upper limit: 0 ~ 2000MΩ; lower limit: 1 ~ 2000MΩ

Test time range / resolution

1~300s 1s/step

Equipment dimensions435MM(W)*150MM(H)*550MM(D)
Equipment weightApprox. 30KGS
Equipment accessoriesPower cord*1, high voltage probe*1, test wire*1, fuse*1

External Wire Connection:


First confirm the power supply standard, AC 220V±10%,50Hz±5%,single-phase; the fuse standard: 5A,slow-blow. Note: terminals on the power supply connection box are marked as: output L, input N, GBI+,GBU+, earth connection clamps are marked GBU-,GBI-, connect the corresponding terminals on the rear panel when use.


Graph: SN9636H Wire Connection