APP Control PIR BLE Motion Sensor Radius 4m 6m Detection Range
Bluetooth Networking Mash App Control Pir Sensor Radius 4-6m
Detection Range
Features of Sensor:
1. Bluetooth networking HAISEN App control.
2. Remote control.
3. Detection Range: 4-6m(Radius).
4. Suitable for tri-proof light.
5. 5 years warranty.
Product Description of Bluetooth Motion Sensor:
Operating voltage | 120-277Vac 50Hz |
Output Peak | ≥3500mV |
Sensitivity | ≥3200V/W |
Stand-by power | <2W |
Switching capacity | 120V:400W (Incandescent), 200W (Controlgear); 277V:800W (Incandescent), 400W (Controlgear) |
Control method | ON/OFF 0-10Vdimming (Sync with bluetooth APP) |
Control line | EU version:Brown L; Blue N; Yellow L’; Red DIM+; Black DIM- American version:Black L; white N; Red L’; Purple DIM+; Gray DIM- |
Infrared Wavelength | 5-14um |
Detection angle | ≤120° (Fresnel lens) |
Engine time | 45±5s |
Operating temperature | -20℃~+45℃ |
Mounting Height | ≤12m(ceiling mounted) |
Detection Range | Radius 4-6m(ceiling mounted) |
Gross wight | 15kg/carton |
Package | Bubble bag+ Clapboard+ Carton(465*300*465mm) |
Detection area | 100%/75%/50%/25% |
Hold time | 5s/30s/1min/30min/5min/10min/20min/30min |
Daylight threshold | 2Lux/10Lux/30Lux/50Lux/80Lux/120Lux/Disable |
Stand-by period | 0s/10s/30s/1min/5min/10min/30min/+∞ |
Stand-by dimming level | 10%/20%/30%/50% |
Certificate | RoHS CE |
Motion detection | 0.5~1.0m/s |
Remote control | HD02R, HD03R ,APP |
IP grade | IP20 |
Warranty | 5 years |
Requirements:
1. 1.6m in height, 65kg in weight, and 0.5/s straight walking
speed;
2. Built-in installation of lamps and lanterns, installation
height: 3m high for ceiling installation, indoor test results,
actual test data subject to the customer's actual test.
Factory Default Setting: Detection area 100%/ Hold time 5s/
Daylight threshold Disable/Stand-by period 0s/Stand-by dimming
level 10%.
ON/OFF Control Detection Area Hold Time Daylight Threshold Warranty
of 5 years
Stand-by Period Stand-by Dimming Level Remote Control Mobile APP
Setting Bluetooth networking
10-15m highbay
The mechanical structure of the Bluetooth motion Sensor:
Three metal mounting brackets (A/C/D) for options. No metal bracket
if no needed.
Wiring diagram of Dimmable Sensor
Detection coverage of Dimmable Sensor:
This figure indicates the maximum distance at the highest mounting
height with 100% sensitivity.
Installation Method:
Bluetooth networking:
1. Search Bluetooth devices, add devices, group devices and
implement APP
management through mobile APP;
2. After the bluetooth devices are grouping with mobile APP,once
the sensors in any direc
tion are triggered, all devices in the same group will receive the
signal and function synchronously.
Bluetooth Networking Function, Application Demo:
With sufficient ambient brightness, even motion get detected,
lights keep off.
With insufficient ambient brightness, all lamps will switch on
simultaneously if any movement get
detected by any master sensor from any direction.
All lamps dim to preset stand-by dimming level if no movement
triggers the sensor after holdtime.
All lamps switch off if no movement triggers after stand-by period.
Stand-by dimming level:
The definition of low output in the standby period.
Application:
1. Automatically ON/OFF function:
The Stand-by period is set to "0s", Daylight threshold is set to
"2Lux/10Lux/30Lux/50Lux/80Lux/120Lux".
Light on when detect movement and off after people leave at night.
Applications: Corridor, Staircase.
With sufficient daylight, With insufficient daylight, After the
last detection and
even when motion detected, when motion detected, light the present
hold time
light remains OFF. ON. elapsed, light OFF.
2. No daylight function
The daylight threshold is set to "Disable".
Light on when detect movement, After people leave, Light off after
stand-by period.
Applications: Dim places such as Basement Parking, Underpass.
When motion is detected, After people leave the After the last
detection and
the sensor will switch on the detection area, light remains the
present hold time
light to 100% brighteness. 100% brightness within elapsed, light
OFF.
hold time.
3. Function Demo - Dimmable control/Corridor function
The Stand-by period is set to "10s/30s/1min/5min/10min/30min",
Daylight threshold is set to "2Lux/10Lux/30Lux/50Lux/80Lux/120Lux".
Light on when detect movement and off after people leave at night.
Applications: Corridor, Staircase.
With insufficient With sufficient daylight, After the stand-by
After last detection, the
daylight, when motion even when motion period, light OFF. light
will be dimmed
detected, light ON. detected, light remains down to the stand-by
OFF. dimming level
(10%,20%,30% or 50%)
after holdtime.
Attention:
1. Please read the instructions carefully before using this product
and keep it well for all users to
read at any time.
2. The sensor should be installed by qualified electrician and
ensure power is off before the
installation.
3. We reserve the right to modify any incorrect text, image and
necessary technical parameters.
4. Any unauthorized modification is forbidden, otherwise all
guarantees will be immediately invalid.
Infrared Sensor Installation Notice:
1.The infrared sensor module shall be exposed.,Fresnel lens should
not be covered by any objects.
2. It shall not be installed and used outdoors, or it will be false
triggered by the influence of ambient temperature.
3. Shall not be installed intemperature sensitive environment such
as heating, air conditioning, refrigerator, stove, etc.
4.Shall not be installed directly against the window to prevent
false trigger caused by the interference of outdoor hot air flow
and
personnel movement.
5. Shall not be installed in the strong airflow place like doorway
or passageway.
6.There shouldn't be any obstacles such as screens, furniture,
large bonsai etc. within the detection range.
7.The direction of human movement has a great impact on the
infrared sensor detection range. It is not sensitive when walk to
the
sensor radially, while it's the most sensitive when walk to the
sensor tangentially or horizontally. Choosing the appropriate