Description

  • Description: AC solution EM for 9-350W LED luminaire.
  • It must connect 0/1-10V dimming wires if power of luminaire>power of EM.

Features

  • UL listed for field or factory installation,CEC title 20 compliant.
  • Compliance with American NFPA 101 life Safety Code.
  • Easy installation, no need to open up a luminaire to connect this devic to the driver, connect with the led lamp directly.
  • With built-in junction box.
  • 2-in-1 LED test switch and indicator light included
  • Manual testing via remote control(optional)
  • Monthly/annual self-testing
  • With multi-protection function:

​ -Battery overcharge protection
-Battery over-discharge protection
-Output overload protection
-Short-circuit protection

-Open load protection

  • 5 years limited warranty


ELECTRICAL SPECIFICATIONS

Input voltage100-347 VAC 50/60Hz
Input Current0.15A max
Input Power12W Max
Power Factor0.7@230Vac,0.6@347Vac
Output Voltage120-200Vdc 250V MAx
BatteryLi-ion
Recharge duration24Hrs
Emergency duration90mins
Ambient temp0-50°C(32℉-122℉)

MODEL SELECTION TABLE

Models

ES-EIB30-01S

ES-EIB40-01S

Emergency wattage

30W



40W



Battery capacity

14.8V/5200mAh
14.8V/6600mAh
Compatible led fixture
30-240W LED lamp with
0-10V dimming or
LED lamp less than 30W
without 0-10V dimming
40-350W LED lamp with
0-10V dimming or
LED lamp less than 40W
without 0-10V dimming


MOUNTING CONFIGURATION


NORMAL MODE
Fixtures will operate normally when power is available. When an outage occurs, the fixture will switch to emergency mode, delivering power to the fixture for up to 90 minutes.

EMERGENCY MODE

1.The emergency battery backup enters the emergency mode immediately after the mains power failure.

2.Stop the emergency and return to the charging state after the mains power call.


SELF-TEST

MONTHLY SELF-TEST
It will automatically perform a monthly self-test every 30 days with a duration of 30S to check whether the emergency function is normal, and automatically restore to normal charging after 30S discharged.
ANNUAL SELF-TEST
An annual self-test will be done every year(12 months) with a duration of more than 90mins to check whether the capacity of the battery pack is normal, and automatically restore to normal charging after fully discharged. (the condition of annual test is that the battery pack is fully charged). If the annual inspection is interrupted, it will be retested after recovery and when the test conditions are met. (Possibility of interruption: such as sudden power failure, sudden manual test).