Add to Cart
The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.
UT55A and UT52A Temperature Controller Features
ITEM | UT55A | UT52A | |
---|---|---|---|
PV input | Input type | 1 Universal input (TC, RTD, mV, V, mA) | |
Indication accuracy | ±0.1% of F.S. | ||
Control scan period | 50, 100, 200 msec | ||
PV/SP data display | 14-segment, 5 digits, Bar graph LCD display | ||
Control outputs (MV) | Type | Relay, Voltage Pulse, Current | |
Algorithm | ON/OFF, PID (Continuous, Time-proportional), Heating/Cooling, Position-proportional | ||
Digital inputs | Number | 3 (Std) 9 (Max) | 3 (Std) 5 (Max) |
Type | SP No.Change, PID No. Change, A/M Change, etc | ||
Digital outputs | Number | 3 (Std) 18 (Max) | 3 (Std) 5 (Max) |
Function | PV High, PV Low, Dev High, etc | ||
Current trans input (option) | Number | 2 | |
Retransmission | Number | 1 | |
Type | PV, SP, OUT, etc | ||
Remote (aux.) input (option) | Number | 1 or 3 | 1 |
Type | 1 to 5 V, etc Only 1 input can be changed to universal input when specified the /DR option | ||
Loop power supply (LPS) (option) | Number | 1 | |
Voltage | 21.6 to 28.0 VDC | ||
Communication (option) | Number | 1 or 2 | 1 |
Type | RS-485, Ethernet, PROFIBUS-DP, CC-Link, DeviceNet | RS-485, CC-Link | |
Other specifications | Power supply | 100 to 240 VAC (+10%, -15%) or 24 VAC/DC (+10%, -15%) (option) | |
Power consumption | Max 18 VA | Max 15 VA | |
Mass | Max 0.5 kg |
Advanced Control
The control mode allows easily configuring settings and making changes with parameters.