SIL2 TUV Fixed Gas Detector

Brand Name:WG Sensor™
Certification:SILII CE
Model Number:HGDS1000
Minimum Order Quantity:1pc
Delivery Time:20-30 days
Payment Terms:T/T, L/C, Western Union
Contact Now

Add to Cart

Site Member
Location: Zhengzhou Henan China
Address: No.169 Xuesong Road National High-tech District Zhengzhou Henan province
Supplier`s last login times: within 3 hours
Product Details Company Profile
Product Details

TUV certified GDS system of Fixed Gas Detectors with SIL II safety level for industrial application


Product Brief Introduction:
HGDS1000 safety control system meets the requirements of system capability of safety integrity level SIL2 with large capacity, high availability, superior performance, fast response characteristics, can be widely used in petrochemical, fine chemical industry, oil and gas pipeline transmission, hospital safety equipment and enterprise ESD system. Control system are composed of controller and the IO module to complete the functions of data acquisition, logic operation, action output, human-computer interaction and so on, so as to realize the security protection function.
Features:

High Availability

(1) Adopt dual rack redundant structure, including power redundancy, controller redundancy and network redundancy.
(2) In redundancy mode, the system can still run when there is a single fault.
Fast Response
(1) The typical time of redundancy switching is 90 ms.
(2) The minimum time of task scheduling is less than100 us.
(3) The fastest control cycle of loop is 50 ms.
Large Capacity
(1) Single-DP network, 124 IO slaves can be added.
(2) The IO capacity supported by the system is more than 10,000 points.
Easy Maintenance
(1) More than 10,000 logs are recorded by logging tools, including abnormal operations, faults and other information.
(2) Module information and diagnostic information of each module can be obtained respectively through Module Information Instruction Library and System State Instruction Library.
(3) Each module is hot-swappable.
(4) Update the system by SD card or HGDS-AutoThink software.

Technical parameters:


Reliability specifications

AC/DC power supply

Voltage: rated AC100V ~ AC240V (root mean square value), tolerance -15% ~ +10% (85VAC ~ 264VAC)
Frequency: rated 50Hz or 60Hz, tolerance-6%~+4%(47Hz~63Hz)

Power supply on Site24V DC (-15% ~ +20%)
System Power Supply24V DC (-15% ~ +20%)
Working Environment Temperature0℃~60℃, EN60068-2-14, Test Nb
Storage Environment Temperature-40 ℃ ~ +70 ℃, EN60068-2-14, Test Na
Humidity5%~95%, no condensation, EN60068-2-30, Test Db
Working Altitude≤2000m
Storage Altitude≤3000m
Electrical SafetyMeet the requirement of IEC 61131-2, IEC 61010-1, IEC 61010-2-201. Enclosed, SELV/PELV circuits.
Isolation withstand voltage (field to system)500V ACt1mistn,leakage current is not more than 5mA
Over voltage levelII
IP protection gradeIEC60529 IP20(the foreign matter more than 12mm can not enter,not waterproof)
Pollution Level2
VibrationSinusoidal vibration (durability)0.5G @ 10 to 150Hz, 3 axis, 20 times per axis, IEC 60068-2-6
Sinusoidal vibration (operation)3.5mm @ 5 to 8.4Hz, 3 axis, 10 times per axis, IEC 60068-2-6
1G @ 8.4 to 150Hz, 3 axis, 10 times per axis, IEC 60068-2-6
shockHalf sinusoidal, 15G peak for 11ms, 3 axis, 18 times in total, IEC 60068-2-27
collision(0.5±0.04)J, 3 times per spot
EMCRadiation emissionIEC 61131-2, EN 61000-6-4, EN 50121-4
Conducted emissionIEC 61131-2, EN 61000-6-4, EN 50121-4
Electrostatic dischargeIEC 61000-4-2 Contact discharge ±6 kV, Air discharge ±8 kV.
Radio frequency electromagnetic field radiation immunity

IEC61000-4-3
80MHz~1000MHz, 20V/m
1.4GHz~2.0GHz, 10V/m
2.0GHz~6GHz, 5V/m
80 % AM (1 kHz)

Power frequency magnetic field immunityIEC 61000-4-8 100 A/m (50 Hz)
Electrical fast transient burst

AC power port:
2kV (5/50 ns, 5 kHz and 100 kHz)
4kV (5/50 ns, 5 kHz and 100 kHz)

Signal port:
2kV (5/50 ns, 5 kHz and 100 kHz)
2kV (5/50 ns, 5 kHz and 100 kHz), DIO with shielded lines

surge

AC power port:
2kV CM, 1kV DM
4kV CM, 2kV DM

Signal port:
2kV CM

RF conducted immunity

IEC61000-4-6
20V, 150 kHz to 80 MHz
80%AM(1kHz)

0Hz~150kHz Common mode conduction immunity

AC power port:
1 V to 10 V increasing with 20 dB/decade (1,5 kHz to 15 kHz).
10 V (15 kHz to 150 kHz)

Signal port:
1 V to 10 V increasing with 20 dB/decade (1,5 kHz to 15 kHz);
10 V (15 kHz to 150 kHz)
10 V (continuous: DC, 16 2/3 Hz, 50 Hz, 150 Hz)
100 V (short duration 1 s: DC, 16 2/3 Hz, 50 Hz)

Voltage dips, short interruptions

0 % during 0.5 cycle
0 % during 1 cycle

40 % during 10 cycles
70 % during 25 cycles
0 % during 250 cycles

TUV certificate:




Company profile:

Henan Weiguo Intelligent Technology Co., LTD., founded in 2015, is an important subsidiary of Hanwei Electronics Group Corporation (Stock no.:300007) in the field of intelligent healthy, safe home and IoT business. Henan Weiguo Intelligent Technology Co., LTD., relying on the core sensor technology, focuses on gas and smoke alarm, air quality monitor, alcohol tester and firefighting products. Based on introduction of featured technology from both Hanwei Electronics Group Corporation and abroad, Henan Weiguo intelligent Technology Co., LTD., has developed into an innovative company with the collection of design, R&D development, production, sales and service. We will always be committed to becoming the leader in intelligent hardware, providing safe, healthy, environmentally friendly and intelligent working and living environment for families and users all over the world.


(Hanwei Electronics Group Corporation (Stock no.:300007), founded in 1998, is an influential manufacturer of gas sensors and instruments in China and a leading supplier of sensor-based IoT solutions in China. Hanwei Electronics Group Corporation is committed to providing perfect solutions for smart city, safe production, environmental protection and people's health.)