DGFC 60KVA-300KVA Reactive Power Compensation Device Low Voltage Dynamic Type

Brand Name:BAIKONG
Certification:IEC,GB
Model Number:DGFC
Minimum Order Quantity:1set(MOQ)
Delivery Time:15Days OR To be negotiated
Payment Terms:L/C, Western Union, T/T
Contact Now

Add to Cart

Active Member
Address: D5-4 Workshop 389 3rd Section, East third Ring Road, Industrial Development Zone ,Pengzhou City, Sichuan Province
Supplier`s last login times: within 14 hours
Product Details Company Profile
Product Details

DGFC 60KVA-300KVA Low-Voltage Dynamic Type Reactive Power Compensation Device


Application


This series of devices regard high-performance single-chip micro computers the basic hardware, adopt AC sampling, digital integration, filtration technology, can trace and compensate the reactive electricity intelligently. This method has prevented the problem caused when contactor input and cut off the capacitor, through compounding switch (input and cutoff mode of combining with crystal braking-tube and contactor ) and input and cutoff over-zero,so as to prevent the "surge current" caused while capacitor inputting. Three is no mechanical movement, and electric arc. No harmonic wave fast compensating speed that is especially suitable for using at the place of frequent inputting and cutting. And this method can lengthen the service life of the main device of capacitor. It has reason-able structure, modern techniques, mainly apples to the low-voltage power network to increase power factor and reduce reactive loss, improve power supply quality. It is the new generation economizing on electricity products and also is one of the advanced compensator both at domestic and inter-national at present.


Model and implication



Main Characteristics


Small volume, convenient for installing and maintenace, good water proof performance, and can be used for both outdoor and indoor.

Controlling parameter full digital operation, convenient for using, the data cannot lose when power off.

Digital display power network power factor, reactive power, voltage, current (one side), control parameter.

With the function of over-voltage, under-voltage judgment displays and fast cut off the compensated capacitor group.

With two working modes of manual and auto compensation.

It has the function of auto selecting the best mode to input and cutoff compens ation according to the result of capacitor group manual input.

With two working modes of cycle or optimizing input and cutoff, the compensation Includes controlling mode of 1:1:1:1, 1:2:2:2, 1:2:4:8, the compensator will automatically distinguish its code working mode of manual input duplexure capacitance value, it works according to the correspondence code mode.

With two working modes of power factor or reactive power;


Compensating mode:


① Phase splitting compensation

② Phase splitting and three-phase compensation

③ Three-phase compensation.


Control mode:


① Crystal braking-tube input and cutoff

② Compound switch input and cutoff


Technical Charactersitics


  • Service conditions: Altitude≤2000m, ambient temperature -25℃~50℃, humidity ≤90% at 20℃; ≤90% at 40℃, Installing gradient ≤5°.
  • Usage voltage range:(0.85~1.10)times rated voltage.
  • Max. Allowable over-current: 1.3 times rated current.
  • Control loop no: 1~12(settable).
  • Input and cutofftime: dynamic state 100ms~30S, static state 1~250S(settable).
  • Under-voltage protection: 340V/180V; return difference 6V.
  • Over-voltage protection: 380-500/230-260V; return difference 6V; (settable).
  • CT variation: 50/5A-3000/5A; (settable).
  • Sensitivity: 100mA
  • Measurement precision:
  • Voltage: ±1.0%
  • Current: ±1.0%
  • Power factor: ±1.0%
  • Reactive power: ±2.0%